User's Manual

d~ë=jÉíÉê=bñÅÜ~åÖÉ
QJO `ÉääåÉí=d~ë=jçÇìäÉ=~åÇ=jÉíÉê=fåëí~ää~íáçå=dìáÇÉ
Confirming Proper Installation Conditions
1Fortheinstallationtoqua lify,confirmallofthefollowingpreexisting
conditions:
–Visuallyexaminetheshutoffforsignsofleakingordisrepair.
–PerformthesnifftestforsignsofgasleaksusingtheNaturalGas
DetectionDevice,andthenthesoaptestontheshutoffandcouplings.
–NoDiversionorTamperingEv
ident‐Visuallyinspecttheservicetothe
meterforsignsofdiversionortampering.
AppropriateAccess‐Confirmthataccesstothemeterallowsaminimum
workareatobeestablished.Minimumworkareaincludeswrench
clearance,accesstoshutoff.
AppropriateService&PipingCondition‐Visuallyinspecttheservice
andpipingageandcondition.Confirmthatserviceandpipingar
efitfor
theremovalandinstallationofa newmeterandthatthereisnopre
existingleaks.
AppropriateMeterOrientation‐Confirmthemeterisinstalled
horizontallyorsuchthatthemeterexchangecannottakeplace.
–Ifanypreexistingconditionsarefoundcont
actyo
urSupervisor
immediately.TheSupervisorwillconfirmyourassessmentandgiveyou
directionforcompletingtheinstallationortoissueaskipcodeinthe
Handheld.
2Setuptheareaforinstallation.Turnallpossiblelightingon(forinsidesets).
Clearanappropriateworkspaceandlayoutalltools,eq
uipment.Pre
parefor
leaksoremergencyshutoff.
Shutting Off the Service
1Notifythecustomerthatgasservic ewillbeinterrupted(reconfirmallgas
apparatusesareoff).Inspectfortheproperoperationofeachgasappliance.
Inspectthemetersetforcorrosion,burialoroverbuilding,damage,improper
installation,misalignment,outdatedregulator(Model1213Bor043R),orthe
smellofnaturalgas.
2 Connectthebondingjumperfromservi
c
erisertothepremiseline.Verifythat
theexistingmeterisoffbyisolating(shutoff)allgasapparatusesandconfirm
thatthereisnoflowonthemeterandregister.Ifthemeterisnotfunctioning
correctly,contacttheSupervisorimmediately.TheSupervisorwillconfirm
yourassessmentandgi
v
eyoudirection.
3Manuallyclosethecustomerʹsshutoffvalve.
–Ifyouhaveanyproblemclosingthevalve,contact yourSupervisorfor
directionwhichmay include,ifapplicable,usingtheoutsidecurbstopfor
shutoff.
–Iftheoutsidecurbstopisactivated,theSupervisorwillnotifytheUtility
Su
pervisor.
4Removetheoriginalmeter.
aUsingapipewrenchandbackup,attempttoloosenthemetercoupling
nuts.
bUsemildtorquebuildingtomoderatesteadytorqueuntilthecoupling
nutbeginstoturn.
cDonotjerkorsnapthewrenches,ordamagecouldoccur.