Landis+Gyr Chapter 2 - GPR2-PT Mounting Instructions
Installation Guide 98-1678 Rev AA 11
NOTE: The four longer security Torx screws are GPR2-PT enclosure cover screws. Cover screws
are included in the 40-2424 GPR2-PT kit.
2. Secure the mounting bracket with GPR2-PT to the pipe.
A. Hold the GPR2-PT bracket assembly against the pipe so that the GPR2-PT is vertical and
upright.
B. Insert V-bolt (28-1319) through the 2 middle holes in the bracket (28-0396).
C. Add flat washers, then split-lock washers. Thread nuts over split-lock washers and tighten to
45 +/- 5.0 in-lbs.
Figure 2 - 4. GPR2-PT/Bracket Assembly for Horizontal Pipe Installation