Chapter 2 - Command Center Deployment/Configuration Landis+Gyr
28 98-1671 Rev AA User Guide
• Select the desired interval from the Frequency drop-down.
D. Click the Schedule Command icon to add the command to the Scheduled Commands list.
Figure 2 - 18. Scheduled Commands
E. (Gridstream endpoints only) Select the Delayed check-box for a command.
6. Repeat step 5 for any additional commands.
7. Select the Endpoint Transmit Interval from the drop-down. This setting determines how often
the endpoint will transfer its readings to Command Center.
8. Select the appropriate RF Network Settings from the drop-down.
9. Select an RF Alarm Definition from the drop-down.
10. Click the Save button to save the new configuration group.
Add Meters to a Meter Configuration Group
Adding meters to a configuration group initiates the configuration process.
1. Click Setup > Groups > Meter Configuration Groups and select the endpoint type.
The Configuration Group screen will be displayed.
Table 2 - 2. RF Network Settings Parameters
Default RF Collector
Configuration
Hunt RFS Residential
Configuration A
Hunt RFS S4
Configuration A
Hunt RFS Gas
Configuration
RF Residential
Configuration A
LG AU Residential
Network
Configuration A
LG RF Commercial
Configuration A
Parameter
Outage Wait Value* 6 6 6 30
Tamper Threshold** 10 0 0 0 30 0 10
Time Synchronization
(X, Y)†
1,1 20, 60 20, 60 20, 60 20, 360 20, 60 20, 1
*Outage Wait Value
The length of time (in seconds) that an endpoint will wait during a power
outage situation before sending an outage notification to Command Cen-
ter.
**Tamper Threshold
The number of reverse pulses of -kWh an endpoint must see within an
interval before triggering a "Tamper Alert".
†Time Synchronization
The number of seconds that the meter time may drift before an automated
time synchronization must be performed (X), or an alert must be gener-
ated and sent to Command Center (Y).