Appendix C - Bench Testing
Network Concentrator User and Installation Guide 98-1013 Rev AF 103
1. From the Main Menu, go to the EEPROM configuration menu and verify the relevant EEPROM
configuration parameters.
2. From the concentrator EEPROM Configuration Menu display the configuration. Scroll down the
page that starts with β+Asap store&forward evt group size [0..65535;default=14]: 14".
3. Verify that the following highlighted parameters are set to 0.
Figure
C.6
CPU Configuration Check
4. Scroll down to the page which starts with the configuration item βGateway Concentrator Num of
Cal objects stored in Flash [default=0]: 0".
5. Verify that the following highlighted parameters are set to the values as shown below.
Figure
C.7
Concentrator Parameters
LAN Health Check
The LAN health is determined from the concentrator's RAMLOG.
1. From the Concentrator Main Menu select option 'd'. The Concentrator Debug Menu appears.
2. Select option 'r', to get to Ramlog Menu.
Use option
βdβ
to dump the
ra
mlog.