Landis+Gyr Chapter 5 - RF Filter Enable/Disable and Battery Replacement Kit
Series IV Concentrator U and I Guide 98-1031 Rev AA 51
4. Remove all eight pan head screws and the battery pack.
Figure 5 - 4. Sample pan head screw location
5. Place the new battery pack in the enclosure base and secure it with all eight pan head screws.
6. Torque the screws to 8 ±.5 in-lbs.
7. Connect the battery cable.
8. Replace enclosure gasket (PN 29-1366) with a new gasket. Do not re-use the old gasket.
9. Attach the enclosure lid to the enclosure base.
10. Secure with all six bolts, nuts, washer-flats, and washers.
11. Torque bolts to 45 ±.5 in-lbs.
12. Affix the new battery date label to the outside of the enclosure.
Figure 5 - 5. New battery date label affixed to concentrator enclosure
Do not pinch the battery cable between the base and the lid. Pinching the
cable can short the battery.