LAKOS Automatic Controller Conguration
For automatic systems only.
Followallinstructionsincludedwiththecontrollerforproperinstallationandset-up.Notethatthe
followingsettingsmustbeveriedbeforeoperatingthiscontroller.Eachofthesesettingscanbe
foundonthebacksideoftheinnercontrolpanel.
Output Voltage
SelectACif24VACsolenoidsareusedonyourbackwashvalves.
SelectDC/DCLifyoursolenoidsareeither12VDCor12VDCLatching.IfpowersupplyisDC/
solar,controllerassumesthatDCLsolenoidsareinuse.
IMPORTANT: Do not mix the type of solenoids in your system. All solenoids must be the
same type (24VAC, 12VDC or 12VDC Latching).
Number of Tanks in Operation
Attachingsolenoidwiringtotheterminalblocksigniesthenumberoftanksoperatinginthesystem.
Pre-Dwell - A set time of 30 seconds for sustained pressure differential (from inlet to outlet) before
controllerinitiatesabackwashcycle.
Dwell-Time - Settimeof60secondsbetweenbackwashingoftanksinasystem.
AUTOMATIC
SYSTEM
Outlet
Manifold
Exhaust
Tubing
Pressure Dierential
Switch
Inlet
Manifold
3 Way Ball
Valve Kit
Outlet (Low) Pressure
Gauge Kit
Water Uptake Kit
Inlet (High) Pressure
Gauge Kit
3/8” Poly Tubing
Backwash Manifold
(NOT SUPPLIED BY LAKOS)
Backwash Valve