PROBLEM POSSIBLE CAUSES SOLUTIONS
Poor Filtration
Consistently High
PressureDifferential
Increasing Frequency
ofBackwashCycle
AutomaticBackwash
Fails to Cycle
Excessiveowthroughlters,causing
“coning” of media sand and/or forcing
contaminantsthroughlteroutlet.
Airintank(s)maycausedisruptionof
the media sand bed.
Incorrect media sand.
Excessively high pressure differential
beforebackwashing,whichforces
contaminantsthroughlterbed.
Insufcientvolumeofmediainlter,
which allows contaminants to pass
through the system.
Excessive contaminant load restricts
owthroughtheltersandprevents
sufcientowforbackwashing.
Insufcientbackwashow.
Inadequate media sand volume, which
mayminimizecoverageofbackwash
owacrosslterbed,creatingdead
spots of accumulated contaminants.
Backwashowordurationisnot
adequatetoushltertanksofall
contaminants.
Insufcientsandvolume.
Increased concentration of
contaminants in water supply.
Controller power may be off or circuit
breakertripped.
Improper setting of differential switch.
Soleniod(s) malfunctioning.
Lossofsufcientpressuretoactuate
valve(s).
1. Reduceowrateoraddextra
ltertank(s).Seepages5 or 6
forowrecommendations.
2. Bleed off trapped air in system.
3. Replace with proper media
sand. Consult your LAKOS
representative.
4. Backwashmoreoftenatlower
differential pressure.
5. Add proper sand media to
tank(s)tospeciedlevel.
1. Draintank(s)andremovehand-
hole access ports. Carefully
skimawayanyexcessorcaked
contaminants from the media
sandbed’ssurface.Return
tank(s)tonormalserviceand
backwashsystem.
2. Readjustbackwashorpartially
closeeldvalve.
3. Follow #1 and add sand media
as necessary.
1. Adjustbackwashowor
duration.
2. Add media sand to achieve
proper volume.
3. Adjustbackwashfrequency
or reduce pressure differential
setting to achieve more frequent
backwashcycles.
1. Be sure wiring is connected
correctly.Resetcircuitbreaker.
Turn on power. Controller may
be faulty and need replacement.
2. Adjust as necessary. Typical is
6-7 psi.
3. Checkconnections,cleanports
andcheckforthesoundofthe
solenoid actuating. Replace
solenoid if necessary.
4. Checklterscreenonwater
uptakekitandhydrauliclinesfor
clogsorbreaks/leaks.Replace
as necessary.
Troubleshooting