Owner manual

LS-651 Rev. (3/13)
Printed on recycled paper
SAMPLE
INSTALLATIONS
GENERAL SPECIFICATIONS
DIMENSIONS
For troubleshooting or special assistance, please contact your LAKOS representative or call us:
Approximate
ta wolF hsawkcaBderiuqeRneercSFSIetaR wolF mumixaM
10 Mesh 30 Mesh Outlet Pipe Weight Backwash Pressure Proper Pressure
Model U.S. gpm m
3
/hr. U.S. gpm m
3
/hr. in mm lbs. kg psi bar U.S. gpm m
3
/hr.
ISF 915 350 80 250 60 6 152 29 13.2 55-80 3.8-5.5 10 2.5
ISF 1415 600 136 500 114 6 152 31 14.0 60-80 4.1-5.5 15 3.5
ISF 1424 1100 250 800 182 10 254 60 27.3 65-100 4.5-6.9 18 4.0
ISF 2424 1900 431 1300 305 12 305 75 34.1 75-100 5.1-6.9 36 8.0
ISF 3434 2700 613 1900 432 16 406 100 45.5 75-100 5.1-6.9 50 11.5
Frame & Propelling Vanes: Reinforced fiberglass composite
End Caps, Screen Outlet, Interior Pipe & Fittings: Stainless steel
Screen: 10 or 30 mesh stainless steel or phospher bronze
Bushings: Pressure-lubricated, ultra-high molecular weight (UHMW) polyethylene
Outlet: All are ANSI compatible flanges
CBA * D E
Model in. mm in. mm in.-NPT in. mm in. mm
ISF 915 15 381 19 483 1-1/4 9 229 10 254
ISF 1415 15 381 24 610 1-1/4 14 356 15 381
ISF 1424 24-1/2 622 24-1/2 622 1-1/2 14 356 15 381
ISF 2424 24-1/2 622 34-1/2 876 1-1/2 24 610 25 635
ISF 3434 24-1/2 622 47 1194 2 34 865 35 889
*Minimum backwash line size. Do not reduce.
1365 N. Clovis Avenue Fresno, California 93727 USA
Telephone: (559) 255-1601
Fax: (559) 255-8093
www.lakos.com E-mail: info@lakos.com
The information, specifications and performance data stated in this literature are representative of engineering and production standards at the time of publication. Despite quality control, slight variations
may occur due to manufacturing, product design improvements and/or sample selection. Actual data may be revised without notice, and you are encouraged to verify pertinent data with the manufacturer
when appropriate.
C*
Backwash
Return Line
Connection
ISF
Screen
Outlet,
connects
to pump
intake
1/4" hose barb fitting for connection of
Automatic Pump Safety Shut-off Control
Separators and Filtration Solutions