User guide
Labconco Instruction Sheet 1115700, Rev J, ECO C066 2 of 5
6. If fuse tip is exposed to corrosive atmospheres, cover with small polyethylene bag
and secure with elastic band for additional protection.
Figure 2
Snuffer – Model 1115002 – Internal Hood Depths of 30", 36" and 48"
Installation-
1. On hoods 4 Ft, 5 Ft and 6 Ft in width, locate one unit on the centerline of the hood per
Fig. 3. Hoods 8 Ft and greater require additional units and should be mounted equal
distance behind the light assembly. NOTE: Protruding discharge nozzle should have
an unobstructed discharge at the desired protection zone.
Figure 3