Original instructions Logic+ Technical Manual and Specifications Type A1 Biosafety Cabinet Models 30132 30142 30152 30162 Type A2 Biosafety Cabinet Models 30231 30241 30238 30248 30251 30258 30261 30268 32259 33259 34259 32269 33269 34269 Type B2 Biosafety Cabinet Models 30348 30368 Cell Type A2 Biosafety Cabinet Models 32239 32249 33239 33249 34239 34249 Type B2 Biosafety Cabinet Models 32348 32368 32348 32368 32348 32368 PURICARE Procedure Station Models 31142 31240 31162 31260 Labconco Corp
Labconco Training Programs: In order to assist technicians gain a better understanding of our products, Labconco Corporation offers Training Seminars at our Kansas City Facility on a regular basis. For further details about these training programs, contact Labconco's Product Service Department at 800-821-5525, or (816) 333-8811 from 7:30 a.m. to 5:30 p.m. C.S.T. Additional Copies: Additional copies of this document can be downloaded from Labconco’s website at www.labconco.com.
Table of Contents Introduction Contacting Labconco 7 7 Section One – Background Information QuickStarts 8 What’s the password? 9 How do I calibrate blower speed, filter life and airflow sensor?10-11 How do I see the current configuration? 12 How do I change the configuration? 13-14 How do I run a diagnostic on the: Sash position switches? 15 Keypad, relays and contact? 16 Canopy Alarm? 17 Airflow Sensor? 18 How do I set up automatic operation of the blower, lights? 19 Logic+ Filter Life Gauge Operation an
Section Three – Installation Unpacking the Biosafety Cabinet Preparing the Biosafety Cabinet for operation Moving and Lifting the Logic Installing the Purifier on an Existing Work Surface Installing the Purifier on a Labconco Base Stand Telescoping Base Stands Manual or Electric Lift Base Stands SoLo Electric Hydraulic Lift Base Stands Connecting the Biosafety Cabinet to Utility Service Lines Optional Ventus Canopy Exhaust Connections Optional Vacu-Pass Cord and Cable Portal Drain Valve Installation (option
Section Five – Certification Procedures for the Logic+ Accessing the Certifier’s Menu Adjusting the Blower Speed Logic+ Filter Life Gauge Operation and Resetting for Local Conditions Adjusting the Optional Inflow and Downflow Values Type A HEPA Filter Leak Test Information If the Logic+ is contaminated Type A HEPA Filter Leak Test Specifications If the Logic+ is uncontaminated Type A Supply HEPA Filter Leak Test Type A Exhaust HEPA Filter Leak Test Type B HEPA Filter Leak Test Information Type B Supply HEPA
Section Seven –Electrical System Service Operations Fluorescent Lamp Lamp Identification Changing the Fluorescent Lamp Lamp Socket Replacement Optional Ultraviolet Lamp Lamp Identification UV Lamp Specifications Changing the UV Lamp Lamp Socket Replacement Electronics Module Access Electronic Module Component Identification Circuit Breaker Resetting a circuit breaker Circuit breaker specifications Testing a circuit breaker Replacing a circuit breaker Power Supply Board Service Operations Fuse Testing & Repl
INTRODUCTION This text is designed for you, the Biohazard Cabinet Certifier. Based on your suggestions, comments, and ideas, Labconco has compiled this information for you to use in the certification or servicing of our Purifier Logic+ Biosafety Cabinets. When you use this document in your office or in the field, we would appreciate your input so that we can make further improvements to future editions.
SECTION ONE – Background Information Quickstart The Logic+ family of Biosafety Cabinets is a significant step forward from our Logicplatformed products. While many internal components are the same or similar, the keypad and display have changed considerably. The high resolution, color display will offer you a more thorough explanation of the cabinet’s operation and status than the previous models ever could. These Quickstarts will help you show you how to answer the questions asked in each case.
Quickstart What’s the password for the Logic+? Like the Logic, the Logic+ models password protects the user from entering the Calibration menu to prevent them from adjusting the blower speed, filter gauge or the airflow sensor readings.
Quickstart How do I recalibrate the blower speed filter life gauge airflow sensor reading of the Logic+? 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. MAIN MENU 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape 4. Press the ▼ button until the Calibration option is highlighted (it will turn white). 5. Press OK/Mute to start the calibration procedure.
Quickstart How do I recalibrate the blower speed filter life gauge airflow sensor reading of the Logic+? - Continued 11. If this is an initial certification or a recertification after HEPA filter replacement, select Reset Filter Gauge to 100%. If this is an annual recertification, select Leave Gauge unchanged. If you want to set the filter gauge at a preset value, select Set Gauge to new setting. Then press OK/Mute.
Quickstart How do I see the Current Configuration of the Logic+? 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. MAIN MENU 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape Service 4. Press the ▼ button until the Current Settings option is highlighted (it will turn white). 5. Press OK/Mute to see the configuration.
Quickstart How do I change the Configuration of the Logic+? 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. MAIN MENU 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape Service 4. Press the ▼ button until the Configuration option is highlighted (it will turn white). 5. Press OK/Mute to alter the configuration.
Quickstart How do I change the Configuration of the Logic+? – continued 9. The first screen allows you to set the Type of cabinet. The only difference between the Type A1 and Type A2 configuration setting is that the airflow velocity limits for normal operation of the optional airflow sensor (because the Type A1 has a nominal inflow of 85 FPM, and the Type A2 is 105 FPM). If the air velocity goes out of range, the alarm will be displayed, but the cabinet will continue to run.
Quickstart How do I run a diagnostic on the sash position switches? MAIN MENU 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape 4. Press the ▼ button until the Diagnostic Diagnostic option is highlighted (it will turn white). 5. Press OK/Mute to enter the Diagnostic submenu.
Quickstart How do I run a diagnostic on the keypad, relays and contacts? MAIN MENU 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape 4. Press the ▼ button until the Diagnostic Diagnostic option is highlighted (it will turn white). 5. Press OK/Mute to enter the Diagnostic submenu.
Quickstart How do I run a diagnostic on the Canopy Alarm? MAIN MENU 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape 4. Press the ▼ button until the Diagnostic option is highlighted (it will turn white). 5. Press OK/Mute to enter the Diagnostic submenu.
Quickstart How do I run a diagnostic on the Airflow Sensor? 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will Service turn yellow). Current Settings 3. Press OK/Mute to enter the Services menu screen. Restore Default Diagnostics Calibration Configuration orto choose, OK to select, MENU to return MAIN MENU 1.Diagnostics MyLogicTM Sash sensors 2. Settings -Relays 3.
Quickstart How do I set up automatic operation of the blower and lights? 1. Press the Menu button. 2. Press the ▼ button until the MyLogic option is highlighted it will turn blue). 3. Press OK/Mute to enter the MyLogic menu screen. 4. Press the ▼ button until the option configure my Logic for use option is highlighted (it will turn white). 5. Press the ▼ button to select either Smart-Start or manual operation of the cabinet blower.
Logic+ Filter Life Gauge Operation and Resetting for Local Conditions The filter life gauge calculates the remaining filter life by measuring and comparing the current motor speed to the initial speed noted at the factory during assembly, and the calculated maximum motor speed, using the formula: 100-(100x (current speed-original speed) ) = % filter life left max. speed-original speed So anything that changes the motor’s current speed, like: Blocking the grille. Raising the air temperature.
QuickChart – Logic+ Type A1 - Imperial Units Model Type Cabinet Size (in feet) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (FPM) grid # of points (rows x columns) Grid distance from back & sides Distance between rows Distance between columns Inflow Data Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
QuickChart – Logic+ Type A1 - Metric Model Type Cabinet Size (in meters) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (m/s) 30132 A1 .91 305 1303_ 30142 A1 1.22 305 1303_ 30152 A1 1.52 305 1303_ 30162 A1 1.83 305 1303_ .279 +/-.03 21 (3x7) 152 141 104 .279 +/-.03 24 (3x8) 152 141 132 .279 +/-.03 30(3x10) 152 141 137 .279 +/-.03 36(3x12) 152 141 140 .432 +/-.03 .283 .122 .115-.129 .432 +/-.03 .375 .162 .153-.172 .432 +/-.03 .468 .202 .190-.214 .432 +/-.03 .561 .
QuickChart - Logic Type A1 BSCs footnotes Logic Model Identification The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top right side of the cabinet. The first two digits of the serial number are the year of production; the next two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
QuickChart – Logic+ Type A2 – Imperial Units Model Type Cabinet Size (in feet) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (FPM) grid # of points (rows x columns) Grid distance from back & sides Distance between rows Distance between columns Inflow Data Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
QuickChart – Logic+ Type A2 – Metric Units Model Type Cabinet Size (in m) Sash Opening (mm) Starting Serial # Downflow Data Nominal Avg. Downflow (m/s) grid # of points (rows x columns) Grid distance from back & sides (mm) Distance between rows (mm) Distance between columns (mm) Inflow Data Nominal Average Inflow (m/s) Sash Open Area (Sq. m) Nominal Avg. Exhaust Vol. (m3/s) Avg. Exhaust Vol.
QuickChart - Logic Type A2 BSCs footnotes Logic Model Identification The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top right side of the cabinet. The first two digits of the serial number are the year of production; the next two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
QuickChart – Logic+ Type B2 Imperial Units Model Type Cabinet Size (in feet) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (FPM) grid # of points (rows x columns) Grid distance from back & sides Distance between rows Distance between columns Inflow Data Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
QuickChart – Logic+ Type B2 Metric Units Model Type Cabinet Size (in m) Sash Opening (mm) Starting Serial # Downflow Data Nominal Avg. Downflow (m/s) grid # of points (rows x columns) Grid distance from back & sides Distance between rows (mm) Distance between columns (mm) Inflow Data Nominal Average Inflow (m/s) Sash Open Area (Sq. m) Nominal Avg. Exhaust Vol. (m3/s) Avg. Exhaust Vol.
QuickChart – Logic+/Cell Logic+ Type B2 BSCs footnotes Logic Model Identification The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top right side of the cabinet. The first two digits of the serial number are the year of production; the next two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
QuickChart – Logic+ PuriCare Procedure Stations Imperial Units Model Type Cabinet Size (in feet) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (FPM) grid # of points (rows x columns) Grid distance from back & sides Distance between rows Distance between columns Inflow Data Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
QuickChart – Logic+ PuriCare Procedure Stations Metric Units Model Type Cabinet Size (in m) Sash Opening (mm) Starting Serial # Downflow Data Nominal Avg. Downflow (m/s) grid # of points (rows x columns) Grid distance from back & sides (mm) Distance between rows (mm) Distance between columns (mm) Inflow Data Nominal Average Inflow (m/s) Sash Open Area (Sq. m) Nominal Avg. Exhaust Vol. (m3/s) Avg. Exhaust Vol.
QuickChart-Logic+ PuriCare Procedure Stations footnotes Logic Model Identification The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top right side of the cabinet. The first two digits of the serial number are the year of production; the next two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
QuickChart – Cell Logic+ Type A2 BSCs Imperial Units Model Type Cabinet Size (in feet) Sash Opening (inches) Starting Serial # Downflow Data Nominal Avg. Downflow (FPM) grid # of points (rows x columns) Grid distance from back & sides Distance between rows Distance between columns Inflow Data Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
QuickChart – Cell Logic+ Type A2 BSCs Metric Units Model Type Cabinet Size (in m) Sash Opening (mm) Starting Serial # Downflow Data Nominal Avg. Downflow (m/s) grid # of points (rows x columns) Grid distance from back & sides (mm) Distance between rows (mm) Distance between columns (mm) Inflow Data Nominal Average Inflow (m/s) Sash Open Area (Sq. m) Nominal Avg. Exhaust Vol. (m3/s) Avg. Exhaust Vol.
QuickChart – Cell Logic+ Type A2 BSCs footnotes Logic Model Identification The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top right side of the cabinet. The first two digits of the serial number are the year of production; the next two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
IDENTIFYING LOGIC+ MODELS The Logic+ platform Biosafety Cabinet can be identified readily by several external features, as shown in Figure 1-1: Serial number beginning with 1303xxxxx Flush-mounted electrical outlets and covers. Color LED display.
SERIAL NUMBER TAGS The model/serial number tag is located on the bottom outside edge of the right corner post. A second tag is located on the front of the electronics module on the top of the unit. This tag includes the unit’s operating voltage and amperage. The model and serial numbers of each unit are also recorded on the unit test report attached beneath the front dress panel.
LOGIC+ MODEL NUMBERING SYSTEM Logic+ units’ model numbers define the configuration of the cabinet. The first five digits define the unit's configuration, while the last four are assigned based on the unit's options and electrical configuration.
Logic+ Data Plate The Logic+ Data Plate contains much of the information required to certify the unit. Information on the plate includes nominal inflow and downflow velocity settings, a description of how to establish the downflow grid and the secondary inflow methodology are also included on the data plate, as shown below. The plate is located in the upper left corner of the dress panel.
Final Inspection and Test Report Form A copy of the Final Inspection Test Report is attached to the blower plenum cover, beneath the front dress panel. The report contains initial setup information on inflow and downflow velocities, and the initial blower torque setting.
Theory of Operation This section offers a brief overview of the theory of operation of the Logic+. Airflow Patterns Figure 1-8 All Logic+ Type A2 cabinets meet the airflow requirements of ANSI/NSF Standard 49:2012. Approximately 55-60% of the air in the cabinet is filtered and recirculated, while 40-45% is filtered and exhausted. ALL Logic+s feature intrinsically safe designs, jacketing contaminated positive pressure areas with negative pressure zones.
ECM Motor The modern Class II Biosafety Cabinet was developed in the early 1960’s as a result of the increased availability of High Efficiency Particulate Air (HEPA) filter technology. The motor of choice at the time to drive the cabinet’s blower was the Permanent Split Capacitor (PSC) type. At the time, the PSC motor offered manufacturers an inexpensive power source whose speed could be electronically controlled to allow for airflow adjustment as the HEPA filter(s) loaded.
Controlling the motor’s operation with a microprocessor adds numerous advantages. Motor speed can be efficiently controlled across a speed range that would damage or destroy a PSC motor. Given enough microprocessor memory and power, the manufacturer can program in any number of userselected programs controlling motor speed, power and even direction of rotation.
The Logic+ has three circuit boards. The ECM microprocessor and power supply board, located in the end of the ECM, the control board on the right side wall, shown in Figure 2-5, and the power supply board assembly, located in the electronics module, as shown in Figure 1-13. Figure 1-13 UV Relay Light Relay Outlet Relay The Logic+ also has an optional contact/RS232 board.
Section Two – Installation Requirements This section offers an overview of site requirements and how to prepare the unit for operation. Prerequisites Before you install the Logic+, you need to prepare the site for installation. Examine the location where you intend to install the cabinet. You must be certain that the area is level and of solid construction. In addition, a dedicated source of electrical power must be located near the installation site.
Location Requirements Note: The biosafety cabinet should be located away from traffic patterns, doors, fans, ventilation registers, fume hoods and any other air-handling devices that could disrupt its airflow patterns. All windows in the room should remain closed. Figure 2-1 shows the preferred location for the biosafety cabinet.
Exhaust Requirements Type A If you intend to connect the biosafety cabinet to the optional VentusTM Canopy Connection Kit, first examine the location to ensure that it accommodates the cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port should be clear of structural elements, water and utility lines, or other fixed obstructions. There should be enough clearance to accommodate a 10-inch diameter duct.
Electrical Requirements The biosafety cabinet models have the following electrical requirements: Table 2-1 Model # Requirements All 3-& 4-foot Type A ending in -00 All 3-& 4-foot Type A ending in -10 All 3-& 4-foot Type A ending in -20, 30, 40, 50, 60, 70 115 VAC, 60 Hz, 12 Amps 100 VAC, 50/60 Hz, 12 Amps 230 VAC, 50/60 Hz, 6 Amps All Type B2 ending in -00 All Type B2 ending in -10 All Type B2 ending in -20, 30, 40, 50, 60, 70 115 VAC, 60 Hz, 12 Amps 100 VAC, 50/60 Hz, 12 Amps 230 VAC, 50/60 Hz, 6 Amps
Service Line Requirements All utility service lines should be ¼ inch O.D., brass, copper, or stainless steel, and equipped with an easily accessible shut-off valve. If the service line pressure exceeds 40 PSI, it must be equipped with a pressure regulator to reduce the line pressure. Note: The use of flammable gases or solvents should be avoided in the biosafety cabinet. Open flame in the cabinet will disrupt the laminar airflow in the cabinet and may damage the HEPA filters.
Section Three – Installation Now that the installation is properly prepared, you are ready to inspect, install, and certify the Logic+ biosafety cabinet. This chapter covers how to: Unpack and move the biosafety cabinet. Install the cabinet. Connect the electrical supply source. Connect the service lines. Connect to an exhaust system (optional for Type As).
Unpacking the Biosafety Cabinet Carefully remove the outer carton and inspect the cabinet for damage that may have occurred in transit. If the biosafety cabinet is damaged, notify the delivery carrier immediately and retain the entire shipment intact for inspection by the carrier. Note: United States Interstate Commerce Commission rules require that claims be filed with the delivery carrier within fifteen (15) days of delivery. Do not return goods without the prior authorization of Labconco.
Moving and Lifting the Cabinet Move the cabinet, attached to its pallet, by using a floor jack, or a furniture dolly underneath the unit. DO NOT move the cabinet by tilting it onto a hand truck. When lifting the cabinet DO NOT lift the cabinet in the middle front area of the hull. Lifting here may bend or distort the bottom of the cabinet, causing damage to the unit. Installing the Biosafety Cabinet on an Existing Work Surface Note: The biosafety cabinet is very top heavy.
Table 3-1 Width 3' Base Stand w/Feet Model # 3401003 4' 3401004 5' 3401005 6' 3401006 Manual or Electric Hydraulic Lift Base Stands These base stands offer infinitely adjustable height between 25.5 and 33.5 inches (648 to 851 mm), giving a cabinet work surface height of 28.0 to 36.0 inches. The height is adjusted either by a manual (hand crank) or electric pump that drives hydraulic rams in the legs of the stands.
Connecting the Biosafety Cabinet to Utility Service Lines Note: Some models have a solenoid valve connected to the service valve on the right side, rear position. The solenoid prevents gas from flowing to the service valve when the unit blower is off. It is the only service valve position that can be fitted with a solenoid valve. Connect the gas service to the solenoid valve.
Optional VentusTM Canopy Exhaust Connection Certain applications such as working with odorous products or volatile toxic materials will require the connection of the biosafety cabinet to an exhaust system. Note: The canopy connection, also referred to as a thimble or air gap connection, allows single or multiple biohazard cabinets to be connected to an exhaust system.
Optional Vacu-PassTM Cord & Cable Portal Use Note: There must be enough clearance to pass the cord or cable between the Logic+’s exterior dress panel and any obstruction. Note: Some Vacu-Pass components and the cord or cable passing through it may become contaminated during use of the cabinet. Ensure all potentially contaminated components are surface decontaminated before handling or removal from the cabinet. 1. Remove the grommet from the liner side wall.
Drain Valve Installation In order to prevent damage during shipping, the drain valve assembly has not been installed. If desired, the valve should be installed after the cabinet is in its final location. To install the valve assembly, follow these steps: Note: The work surface is heavy. Use caution when handling it. 4. Lift the work surface out of the biosafety cabinet by lifting on the knobs at the front of the work surface. Steady the work surface while pulling it straight out the front of the cabinet. 5.
Section Four Initial Operation of the Logic+ This section will take you through the steps to begin initial operation of the Logic+, with an explanation the controls, display and options, in order to prepare the unit for its initial certification. System Reset Switch The biosafety cabinet has a system reset switch for resetting its microprocessors. The switch is located on the front of the electronics module, on top of the cabinet, as shown in Figure 4-1.
Information Center The Information Center is an LCD display located on the right side wall at eye level. When the blower is started, the words “please wait” will be displayed, as shown in Figure 4-2. After approximately 90 seconds, the display will switch to normal operation. The display provides a clock, the remaining filter life, the cabinet’s current status, inflow and downflow velocities (if equipped with the optional airflow sensor), as shown in Figure 4-3.
Alarm Screens Sash is too high The sash is open too far for safe operation. Airflow Alert The airflow patterns in the cabinet have changed, resulting in a sudden change in the motor speed. This is most likely due to a blockage of the grille or the exhaust filter outlet. It may also be caused by removal of the work surface while the cabinet is in operation.
Operating the Sliding Sash The counterbalanced, anti-racking sash mechanism requires only a few pounds of force to move the sash up or down. You can open or close the sash smoothly with one or two hands positioned on either handle. The sash position alarm and safety interlock system senses the sash position and acts appropriately. The biosafety cabinet has been programmed to operate at either an 8-, 9, 10- or 12-inch (203-305 mm) sash opening, depending on model.
The Logic+ Touchpad The touchpad of the Logic+ is shown in Figure 5-6. Take a moment to get familiar with the buttons, their locations and functions. Also familiarize yourself with the display located on the right side wall. The display will report system functions, such as filter capacity, timer displays, alarm or error messages, as well as icons that illuminate when cabinet functions such as UV light and blower are operational. Figure 5-6 Blower Button – Starts or stops the cabinet blower.
Navigating the Logic+ Menu Screens MyLogicTM allows you to use the Smart-Start or Night-Smart features that activate functions automatically when the sash is opened or closed. If equipped, the UV lamp can be programmed to operate for a given time interval when the sash is closed, before it shuts off. NOTE: When you are in the menu mode, if a selection is not made within 30 seconds, the display will reset back to display mode. Keypad operations are shown as blue bold italic.
Navigating the MyLogicTM Menu Screens The MyLogic screens will allow you to set the cabinet’s clock, and to personalize its operation. Please note all MyLogic screens have a blue background. Setting the Clock Using the ▲ and ▼ buttons on the touchpad, highlight the MyLogic option-it will turn blue when selected. Press OK/MUTE to enter the first MyLogic screen: OK/Mute Using the ▲ and ▼ buttons on the touchpad, highlight set the clock -it will turn white when selected.
Configuring the Logic+ In the first MyLogic screen, use the ▲ and ▼ buttons on the touchpad to highlight configure my Logic for use -it will turn white when selected. Press OK/MUTE to enter the first configuration screen: The first screen gives you the option of activating the Smart-Start option for the blower; if you want the cabinet blower to start every time you raise the sash, select start, and then press OK/Mute. If not start is selected, then the blower must be manually started from the keypad.
If you choose to use Night-Smart option for the UV lamp, this screen allows you to control the time the UV lamp will remain on after the sash is closed. Use the ▲ and ▼ buttons on the touchpad to cycle through the time intervals available, and then press OK/MUTE to select it. The screen will then return to the first MyLogic screen. Navigating the Settings Menu Screens The Settings screens will allow an administrator to set some of the cabinet’s operational parameters.
Startup tone Using the ▲ and ▼ buttons on the touchpad, highlight the Startup Tone option-it will turn white when selected, and then press OK. Using the ▲ and ▼ buttons on the touchpad, highlight either Turned on or Turned off option. When turned on, an audible beep will sound during the first 90 seconds of blower operation to caution the user that the unit is not yet ready for use. Security Lock Note: The Security Lock feature “locks” the keypad to prevent unauthorized use of the cabinet.
UV Settings For models equipped with the optional UV light the Logic+ has an integral UV light maintenance system. It allows you to define how many hours you want the UV lamp to operate before receiving a reminder to replace it, a way to monitor how many hours the lamp has been on, and the means to reset the UV lamp hourmeter. UV Lamp Hourmeter This display only shows how many hours the UV lamp has been lit, and how many hours remain until you will receive a warning to replace the lamp.
Timer Operation NOTE: The timer button allows activation of an interval (countdown) or stopwatch (elapsed) timer. The timers cannot be operated simultaneously. To access the main timer menu, press the Timer button anytime during normal operation. The main timer menu is shown on the LCD display. Use the ▲ and ▼ buttons to highlight the Interval or Stopwatch Timer. Press the OK/MUTE button to select the highlighted timer function. Interval Timer Operation 1.
Section 5 Certification Procedures for the Logic+ This section will outline test procedures to validate the performance of the Logic+. Note: These are the only Labconco-approved test procedures for validating the performance of the Logic+ Biosafety Cabinet. Other test procedures may yield different or inaccurate test results. NOTE: In order to properly certify the Logic+, you must obtain a Logic+ Certifier Kit, Labconco P/N 3858400.
Logic+ Filter Life Gauge Operation and Resetting for Local Conditions The filter life gauge calculates the remaining filter life by measuring and comparing the current motor speed to the initial speed noted at the factory during assembly, and the calculated maximum motor speed, using the formula: 100-(100x (current speed-original speed) ) = % filter life left max. speed-original speed So anything that changes the motor’s current speed, like: Blocking the grille. Raising the air temperature.
Adjusting the optional inflow and downflow values Note: This step is only available if the optional airflow sensor is installed. 1. Using the ▲ or ▼ buttons, increase or decrease the displayed inflow velocity until it matches the observed value, then press “OK/Mute” to confirm the value. The display will now change to downflow velocity calibration screen. 2.
Table 5-1 Type A HEPA Filter Leak Test Specifications Cabinet Width (Feet) Sash Height (inches) Air Displacement (CFM) Laskin Nozzles needed Calculated aerosol conc. (ug/l)1 Actual aerosol conc. (ug/l)2 1. 2.
If the Logic+ is Uncontaminated (Establishing an Upstream Concentration) The Purifier utilizes a unique aerosol access tube for sampling the upstream concentration of aerosol. If after reading these instructions, you have further questions, please contact Labconco's Product Service Department. Note: The access tube contains contaminated air under positive pressure. DO NOT access this line until the cabinet has been decontaminated. 1. Remove the work surface by lifting the handles on either end.
Type A Supply HEPA Filter Test Downflow Diffuser Removal 1. Remove the diffuser by raising the sash as high as it will go, and then removing the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-3. Figure 5-3 Removing the diffuser acorn nuts (Dress panel and lamps removed for clarity only). Note: The diffuser acorn nuts are secured to the studs with a removable thread locking compound to prevent them from vibrating loose during shipment of the Logic+.
4. Open the following number of Laskin nozzle(s): For all 3-foot Logic+ models – 1 nozzle For all 4-, 5- and 6-foot Logic+ models – 2 nozzles 5. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG. 6. Scan the downstream side of the HEPA filter by passing the sampling nozzle of the gun in slightly overlapping strokes over the entire surface of both of the filters, with the sampling port not more than 1 inch from the surface of the filter media.
Type A Exhaust HEPA Filter Test Opening the Exhaust HEPA Filter Cover If there is sufficient overhead clearance (18 or more inches) – 1. Loosen the two Phillips screws on the front sides of the filter cover, as shown in Figure 5-7. Tilt the cover back access the downstream side of the filter, as shown in Figure 5-8. Figure 5-7 Loosen these screws to tilt the cover back. Remove these acorn nuts to remove the cover. If there is insufficient overhead clearance – 1.
2. The Logic+ is now ready for the HEPA Filter Leak Test. Set the photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the sampling port of the pistol. 3. Open the following number of Laskin nozzle(s): For all 3-foot Logic+ models – 1 nozzle For all 4-, 5- and 6-foot Logic+ models – 2 nozzles 4. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG. 5.
Type B HEPA Leak Test Information All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012. Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding. Type B Supply HEPA Filter Leak Test All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012. Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding.
Figure 5-10 3. Pull the tube toward the front of the unit. Remove the access tube cover. 4. Using an appropriate photometer, connect the unit's upstream line to the access tube. Note: Keep the photometer sampling tube as short as possible. It should never exceed 6 feet maximum. 5. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting. 6.
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting. 2. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level. 3. Establish the 100% and 0% concentration levels for the photometer. 4. Remove the diffuser by raising the sash as high as it will go, and then removing the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-11.
7. Open one Laskin nozzle. 8. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG. 9. Scan the downstream side of the HEPA filter by passing the sampling nozzle of the gun in slightly overlapping strokes over the entire surface of both of the filters, with the sampling port not more than 1 inch from the surface of the filter media. Scan the entire periphery of the filters and the gaskets between the filter frame and the Logic+ frame.
Type B2 Exhaust HEPA Filter Leak Test All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012. Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding. Note: If so equipped, the prefilter element on the towel catch should be removed, and the aerosol generator should be placed nearby to inject the aerosol as shown in Figure 5-15.
4. Locate a sampling port downstream of the exhaust HEPA filter. The sampling port should ideally be at least 10 duct diameters from any elbow and 10 duct diameters downstream of the filter. 5. The Logic+ is now ready for the Exhaust HEPA Filter Leak Test. Set the photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the sampling tube. 6. Open the Laskin nozzle(s). 7. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG. 8.
Downflow Velocities All Logic+ models, EXCEPT 30248xx80) are classified as having uniform downflow, and the average downflow velocity for all models is 55+/-5 FPM, tested as per ANSI/NSF Standard 49:2012. All readings should be in a plane 4 inches above the bottom edge of the sash, and the UV Lamp, IV bar and all other accessories must be removed before performing downflow test. The test grid dimensions are outlined in Table 5-4.
Figure 5-17 Acceptance Average downflow shall be 55 +/-5 FPM with all test points being within +/- 16 FPM. Inflow Velocity Calculation - Primary Method Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow value. The average inflow velocity for Logic+ A2 and B2 models is 105 ±5 FPM, and Type A1s are 85+/-5 FPM. It should be determined by converting the inflow volume to the average inflow velocity.
Table 5-5 Inflow Test Specifications – 8 inch Sash Opening Width (feet) Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol. Range (CFM) 3 105+/-5 4 105+/-5 5 105+/-5 6 105+/-5 2.03 213 2.69 283 3.36 353 4.03 423 203-223 269-296 336-370 403-443 Inflow Test Specifications – 9 inch Sash Opening Width (feet) Nominal Average Inflow (FPM) Sash Open Area (Sq. Ft) Nominal Avg. Exhaust Vol. (CFM) Avg. Exhaust Vol.
Inflow Velocity Calculation - Secondary Method If the primary method cannot be performed, the secondary inflow calculation method should be used. The secondary method uses a hot wire thermal anemometer. In this method, the sash is lowered, and a series of velocity readings are taken at the front of the unit. NOTE: You must use Labconco holder P/N 3836405 to perform this test properly.
Figure 5-19 The Sensor Distance, as described in Table 5-6, using the slots cut in the 6-foot Logic template. 4.00-inch mark 3.25-inch mark Figure 5-20 The Sensor Distance, as described in Table 5-6, using a scale.
Table 5-6 Secondary Inflow Test Specifications – 8 Inch Sash Opening Cabinet Width (feet) Sash Opening Template1 Sensor distance (inches)5 # of Test points Test point location Nominal Avg. Inflow Vel. (FPM) Avg. Inflow Vel. Range (FPM) Correction Factor (CF) Average Inflow Volume Range (AIV) (Avg. velocity x CF) Sash Open Area (Sq. Ft) Inflow Velocity Range (AIV / Sash open area) 3 3+ 4 6 * 213 203-223 1 203-223 2.03 100-110 4 4+ 3.25 8 * 283 269-296 1 269-296 2.69 100-110 5 5+ 3.
1. Locate the single row of holes at the front of the grille. Mark the 6th hole from 2. 3. 4. 5. 6. 7. 8. the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (for a 3-foot cabinet, for example, mark the first 3 points). Repeat for the opposite side, as shown in Figure 5-21. Start the Purifier, and let it operate for at least 5 minutes.
Type B2 Total Exhaust Volume The total volume of air exhausting from the cabinet can be determined as follows: Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow value. Note: The exhaust volume noted with a DIM on the front of the cabinet may not agree with the value obtained from a traditional Pitot tube or thermal anemometer traverse reading of the exhaust duct. 1. Shut off the cabinet blower. 2. Remove the prefilter element from the top of the cabinet. 3.
Work Area Air Cleanliness Test (optional) If the customer wants to verify air cleanliness in the work area, use the following procedure: 1. Mark test points at the geometric center of the work surface, and midway between the center test point and each side wall. 2. Place a particle counter pickup a test point, at a height of 16 inches above the work surface, pointing into the airflow, as shown in Figure 5-23. Take three samples of 1.0 ft3. Repeat for each test point. 3. Average the results.
Fluorescent Light Level (optional) The fluorescent light intensity should be measured as described in ANSI/NSF Standard 49:2012, Annex F. NOTE: The light meter should be color- and cosign corrected for accurate readings. 1. Test points should be marked along the centerline of the work surface, starting 6 inches from the side wall, with subsequent points 12 inches apart until the center of the work surface is reached. Repeat for the other side of the work area. 2. Take background readings at the test.
Vibration (optional) The vibration level should be measured as described in ANSI/NSF Standard 49:2012. Note: The vibration meter should have a range of 20-20,000 Hz, and have an output in displacement. 1. Vibration level should be recorded from a single point, on the geometric center of the work surface. 2. Take a background reading with the cabinet blower off at the test point. 3. Start the cabinet blower, and take a vibration reading. Acceptance Vibration should be less than 0.
Ground Fault Circuit Interrupter Test (115/100 Volt models only) Note: The GFCI tester must be able to simulate a fault of 3mA. 1. Place the tester into any of the Logic+’s outlets. The indicator lights of the tester should indicate normal function, and the GFCI’s indicator LED should be lit. 2. Press the test button of the tester. The indicator lights should now indicate the circuit is inactive, and the GFCI indicator LED should be off. 3. Reset the GFCI by pressing the RESET button on the right outlet.
Section 6 Logic+ Service Operations This section will review the tools needed, and common service operations for the Logic+.
Figure 6-2 To reinstall the panel, reverse these steps, ensuring that the plastic pin in the top corners of the dress panel properly engage the corner posts. Side Panel Removal Note: The side panel(s) must be taken off to remove the Logic+ from its pallet. 1. Remove and save the two Phillips screws on the front edge of the side panel. 2. Pivot the front of the panel away from the cabinet.
Corner Post Lower Trim The corner post lower trim pieces are secured to the corner post by a single machine screw and lock nut. When properly positioned, the trim piece fits tightly against corner post. See Figure 6-3. Figure 6-3 Use a 3/8” wrench and Phillips screwdriver to adjust the corner post screw. Note: DO NOT over tighten the screw; damage to the trim piece may occur.
Sash Operation The Logic+ sash uses a deadweight-counterbalanced system. The system consists of two separate weights on either side of the liner. Both weights are synchronized by a locked axle-pulley system. Both pulleys are fixed to the axle so that both weights must move together, preventing the sash from racking. Adjustment There are no adjustments for the width of the sash track. There should be approximately 1/8-inch lateral play of the sash in its track.
Sash Position Switches Two microswitches are used to indicate the sash position. The switches are the same, Labconco part # 3832400. A photo of both switches is shown in Figure 6-6. Figure 6-6 Sash Closure Position Switch Sash Operating Position Switch Sash Closure Position Switch The sash closure position switch signals the display microprocessor that the sash is open or closed allowing proper operation of the Blower, fluorescent or UV lights. It is wired in the normally open configuration.
Figure 6-7 Sash Closure Position Switch properly actuated against the sash weight Figure 6-8 Sash Operating Position Switch properly actuated against the sash weight 102 Product Service 1-800-522-7658
Sash Cable Retainer The sash cable retainers are located at the top of each sash pulley, as shown in Figure 6-9. If the retainer needs adjustment, Use a 3/8-inch wrench to loosen the bolt securing the retainer and adjust it until it lightly touches the pulley. Retighten the bolt. Figure 6-9 Type A Exhaust Damper Adjustment The exhaust damper adjustment bolt is located on the left side of the blower plenum cover, in the center of the orange damper bolt seal.
Type A Exhaust Damper Seal Installation The exhaust damper seal is a silicone seal, permanently bolted to the plenum inside the cabinet. CAUTION: The damper seal is permanently attached to the plenum in the cabinet. NEVER attempt to pull the seal out of the cabinet; the seal will be damaged or destroyed. CAUTION: The inside surface of the damper seal may be contaminated. DO NOT disrupt the seal until the cabinet has been properly decontaminated. Installing the seal Figure 6-11 1.
Type A HEPA Filter Replacement CAUTION: The cabinet must be properly decontaminated before servicing the supply HEPA filter. Following replacement of a HEPA filter, the cabinet must be recertified. CAUTION: Always remove the exhaust HEPA filter first. The exhaust filter pan or plenum can be damaged if the plenum is raised with the Exhaust HEPA filter in place. CAUTION: HEPA filters can be awkward to handle and heavy. Use appropriate lifting techniques to remove and handle it.
Figure 6-14 Figure 6-15 5. Remove the last two screws. Gently rock the cover, slide it to the left or right, and swing it out and away from the unit. NOTE: During disassembly, the blower plenum cover can rest on the center sash support, as shown in Figure 6-16, to allow repositioning of the panel or your grip on it. Figure 6-16 Center Sash Support 6.
6. Using a 1/2 -inch socket or wrench, loosen the four exhaust filter sealing bolts located at each corner of the exhaust filter tray, as shown in Figure 6-17, at least 1/2 inch. This releases the exhaust HEPA filter from the cabinet. Figure 6-17 Exhaust HEPA Filter bolts (2 per each side) 7. Pull the exhaust HEPA filter straight out of the cabinet. To Remove the Exhaust HEPA Filter on 3-foot models: 1. Follow steps 1-5 as above. 2.
Figure 6-19 Exhaust HEPA Filter bolts 4. If you choose to remove the exhaust filter pan, remove the sealing bolts, lift the pan straight up, and then pull it forward and out, as shown in Figure 6-20. 5. When reinstalling it, ensure all four edges of the pan are OUTSIDE the sealing edges of the plenum, as shown in Figure 6-21.
To Remove the Supply HEPA Filter: 1. With the exhaust filter removed, use a 1/2-inch socket or wrench to tighten the three plenum lift bolts located as noted in Figure 6-22. This will lift the plenum off of the supply HEPA filter. Remove the Supply HEPA filter retainers on the front of the plenum. 2. Slide the supply HEPA filter straight out the unit. 3. With the HEPA filters removed, inspect the filter shelf and the exhaust filter tray for damage.
4. Sequentially tighten the four exhaust filter sealing bolts located at each corner of the exhaust filter tray until the exhaust filter gasket is compressed no more than 50%. The exhaust filter sealing bolts should only be tightened enough to ensure a proper seal of the exhaust HEPA filter. At maximum tightness, the exhaust filter's gasket should be compressed to 50% of its original thickness. NEVER tighten the bolts beyond this setting. 5.
Type B2 Prefilter Replacement NOTE: The prefilter is not washable; it must be replaced when it becomes dirty. 1. Shut off the cabinet blower. 2. Using an appropriate step or ladder, remove the two wing nuts that secure the prefilter, located next to the electronics module, as shown in Figure 6-24. 3. Remove and discard the prefilter, and replace it with a new one. Retighten the two wing nuts that secure the prefilter.
Figure 6-25 Exhaust HEPA Filter bolts (two in each side of the exhaust connection) To Install an Exhaust HEPA Filter: 1. Slide the new exhaust HEPA filter all the way into the pan. 2. Sequentially tighten the four exhaust filter sealing bolts located at each corner of the exhaust filter tray until the exhaust filter gasket is compressed no more than 50%. The exhaust filter sealing bolts should only be tightened enough to ensure a proper seal of the exhaust HEPA filter.
3. Remove the last two screws. Gently rock the cover, slide it to the left or right, and swing it out and away from the unit. 4. Use 1/2- and 7/16-inch sockets or wrenches to tighten the three plenum lift bolts located as noted in Figure 6-27. This will lift the plenum off of the supply HEPA filter. Remove the Supply HEPA filter retainers on the front of the plenum, if present. 5. Slide the supply HEPA filter straight out the unit. 6. With the HEPA filters removed, inspect the filter shelf for damage.
Motor/Blower Replacement Caution: The cabinet must be properly decontaminated before servicing the motor/blower. The cabinet blower motor's bearings are sealed and require no lubrication. DO NOT attempt to lubricate them. To replace the Motor/Blower: 1. Unplug the cabinet. 2. Remove the front dress panel as shown in Figure 6-1. 3. Loosen all of the Phillips screws on the blower chamber cover. Remove all of the screws except two screws on the top center of the panel. This will support the panel. 4.
7. Using a 1/2-inch wrench, remove the two upper and one lower blower mounting bolts, as shown in Figure 6-29. Figure 6-29 Blower Mounting Bolts The motor/blower assembly is heavy. Handle with care. 8. While supporting the blower assembly, pull the assembly straight out the plenum, as shown in Figure 6-30. Figure 6-30 9. To replace the motor/blower assembly, reverse the above procedure. Note: During reinstallation of the blower assembly, angle the rear blower bracket into the plenum blower opening.
Work Surface Removal Note: The work surface of the cabinet must be thoroughly decontaminated before removing it. 1. Lift the front edge of the work surface straight up by grasping the knob handles at either front corner. 2. Pull the work surface straight out, letting its rear edge rest on the center support underneath. 3. Reinstall the work surface by resting the bottom on the center rail while pushing it back into the cabinet.
Towel Catch Removal Although not normally required, the towel catch can be removed for cleaning, inspection, etc. Note: The work surface of the cabinet and the towel catch must be thoroughly decontaminated before removing either. Although not normally required, the towel catch can be removed for cleaning, inspection, etc. Note: The work surface of the cabinet and the towel catch must be thoroughly decontaminated before removing either. 1. Remove the work surface as described above. 2.
Diffuser Removal Caution: The diffuser should be surface decontaminated before removal. Note: If an IV bar is in place, it will have to be removed first. 1. Raise the sash to its fully open position. 2. Support the front edge of the diffuser while removing the two 7/16-inch acorn nuts on the front of the diffuser, as shown in Figure 6-33. Figure 6-33 Removing the diffuser acorn nuts (Dress panel and lamps removed for clarity only).
4. To reinstall the diffuser, ensure that the two holes on the back edge of the diffuser align with the diffuser support pins on the rear wall of the work area, as shown in Figure 6-35. Figure 6-35 Diffuser pins engaging the holes in the rear of the diffuser.
Preparing the Logic+ for Gaseous Sterilization Note: This section only reviews the steps required for preparing the Logic+ for Gas Sterilization. Thoroughly understand the sterilization procedures and protocols supplied by the manufacturer of the sterilizing system before attempting this operation. 1. Unplug the Logic+ from electrical power. 2. Thoroughly surface decontaminate the working area of the cabinet. In order to get a complete seal on the front of the cabinet, do the following: 1.
Section Seven – Electrical System Service Operations NOTE: In order to properly service the Logic+, you must obtain a Logic+ Certifier Kit, Labconco P/N 3858400. Qualified certifiers can obtain this kit by contacting Labconco Customer Service Department at 800-821-5525. Fluorescent Lamp Lamp Identification All Logic+s use dual fluorescent lamps. The lamp information is shown in Table 8-1.
Lamp Socket Replacement 1. 2. 3. 4. Unplug the Logic+ Remove the dress panel as noted in Figure 6-1 Remove the fluorescent lamps from the sockets. To replace a socket, insert a small straight bladed screwdriver into the socket near the lamp wire, as shown in Figure 7-1. 5. Press the wire into the new socket. 6. Reassemble the unit. Figure 7-1 Optional Ultraviolet Lamp Lamp Identification All Logic+s use a single 30-Watt germicidal lamp. The lamp information is shown below.
Changing the UV Lamp Note: For optimum performance, the UV lamp should be changed on an annual basis. Caution: The UV lamp and the work area of the cabinet must be thoroughly surface decontaminated before removing the lamp. 1. 2. 3. 4. Unplug the Logic+. Raise the sash to its full open position. Surface decontaminate the UV lamp and the work area of the cabinet. Remove the UV lamp by rotating it 90 degrees and lifting it straight up and out of its sockets. 5.
Electronics Module Access The Electronics module is located on the top right side of the cabinet. To access the module, do the following: 1. Unplug the Logic+, either at the wall, or at the power cord inlet at the back of the electronics module, as shown in Figure 7-2. 2. Remove the three 7/16-inch acorn nuts and lock washers that secure the module. 3. Tip the module on its side, and secure it so it does not fall.
Circuit Breaker Resetting a circuit breaker To reset any of the circuit breakers located on the left side of the electronics module, as shown in Figure 7-4, depress the white button until it sets. Figure 7-4 Circuit Breakers- The front breaker protects the electrical outlets, the rear breaker protects the motor and lights. Circuit Breaker Specifications Circuit breaker specifications are shown in Table 7-2, below.
Circuit Breaker Specifications, 230 VAC Cabinet Width (feet) Motor/Light Breaker Rating, Amps Motor/Light Breaker, Labconco Part # Motor/Light Breaker, Mechanical Products Part # Outlet Breaker Rating, Amps Outlet Breaker, Labconco Part # Outlet Breaker, Mechanical Products Part # 3 4 4 4 5 5 6 5 1327209 1327209 1327204 1327204 1600-062040-007 1600-062040-007 1600-062050-007 1600-062050-007 3 1327200 3 1327200 3 1327200 3 1327200 1600-062030-007 1600-062030-007 1600-062030-007 1600-06203
Power Supply Board Service Operations Fuse Testing & Replacement The Power Supply Board is protected by an integral 5 x 20mm, fuse, rated at 2.5 Amps at 250 volts, as shown in Figure 7-5. The fuse is tested with a standard continuity meter. Any resistance across the fuse indicates a defective fuse and should be replaced.
Display Board Service Operations Display Board Diagnostics is addressed in the section on Touchpad Test Operations. Touchpad Connections To correctly connect the touchpad to the Display Board, orient the ribbon connector so the metallic side of the connector is away from the side of the Logic+, as shown in Figure 7-6. Figure 7-6 Aligning the touchpad ribbon connector and the circuit board (metal frame and other wiring omitted for clarity).
Diagnostic Operations The available diagnostic tests are outlined in the QuickStart section of this manual. Motor Service Operations NOTE: Use caution when measuring test voltages to avoid short circuits. The ECM does not require routine service. The motor bearings are permanently lubricated, and do not require additional lubrication. Motor Testing For the ECM to operate properly, the motor must receive: 1. Line voltage across pins 4 (black wire) and 5 (white wire) through the power connector. 2.
Figure 7-7 15 pin connector 4. Disconnect the 15-pin connector, and install the pass-thru harness, as shown in Figure 7-8. Plug the Logic+ back in. With the meter set on AC voltage, verify the AC mains line voltage is present within ± 5 VAC when the AC voltage is measured across pin 2 (black wire) and pin 3 (white wire) on the 3-pin connector, as shown in Figure 7-9. Figure 7-8 Pass-thru Harness installed Figure 7-9 Measuring Line voltage 5.
6. Next, connect the meters + DC voltage lead to pin 6 (yellow wire) and verify there is ± 24 Volt DC ± 5 Volts DC, as shown in Figure 7-10. The presence of 24 Volt DC on this yellow wire tells the motor to start. Figure 7-10 Measuring 24 VDC voltage 7. Next, move the meter’s + DC voltage lead to pin 5 (purple wire) [the meter’s lead is still connected to pin 8 (brown wire)]. Note the DC voltage, since the motor’s speed is determined by the pulse width modulated signal on this contact.
Motor Output Signal Testing Use the Service Menu’s “Current Settings” screen to access the Motor Speed Factor, Motor RPM, average RPM, and new filter RPM. Figure 7-11 shows the LCD screen and the location of these values.
Wiring Diagrams -115 VAC Models Product Service 1-800-522-7658 133
Wiring Diagrams -230 VAC Models 134 Product Service 1-800-522-7658
Section Eight – Purifier Logic+ Accessories VentusTM Canopy Connection Kit P/N 3889200, -01, -02, -03 Section 1. – Theory of Operation The Ventus canopy system consists of a high efficiency, low profile canopy that interfaces directly with the Logic+’s control board. Ventus offers several features that are a distinct improvement over prior canopy designs: The alarm system is simple, rugged, and durable; a magnetic reed switch located on the intake valve.
Section 1. - Canopy Installation Procedure 1. Turn off the Biosafety Cabinet. 2. Locate and remove the four acorn nuts and lockwashers that secure each side of the exhaust cover and the angle bracket to the top of the unit. 3. Lift the cover and angles straight up off of the top of the cabinet. Keep the nuts and washers; you may also want to retain the cover and angles for the future, if the cabinet will be disconnected from the exhaust system. 4.
Section 2. – Exhaust Damper Installation Procedure NOTE: Proper installation of the canopy damper is crucial for proper alarm system operation. If you have questions, please call our Product Service Department. Labconco offers an optional gas-tight exhaust damper, p/n 3776800. An equivalent damper can be used if desired. 1. Install the damper on top of the canopy, ensuring that the control handle faces the front of the unit as shown below. 2.
Section 4. – Calibration of the Unit with a Canopy Connection Set-up cabinet inflow and downflow air 1. Connect the Unit to the exhaust system but do not turn on the external exhaust blower. Plug the unit in but do not turn it on. 2. Lift the exhaust relief valve(s) wide open and tape in position. Prop open the Inlet valve to prevent a canopy alarm. Open the exhaust damper control lever to the fully open position. 3. Turn on the unit and allow unit to operate for at least 5 minutes. 4.
Canopy Exhaust Volume Measurement 7. Remove the tape holding the exhaust relief valve(s) open and close them. Close the intake valve. Turn on the external blower. 8. Position the probe of the thermal anemometer against the intake slot on the right side of the canopy, such that the sensor portion of the probe is centered front to back of the opening, with the bottom of probe sitting on the bottom of the inlet wrapper, and in the plane of the canopy side wall, as shown. 9.
Section 5 – Reconfiguring the Unit for Operation with a Canopy Connection Note: After canopy installation, you MUST reconfigure the Logic+ to have a canopy. 1. Press the Menu button. 2. Press the ▼ button until the Services option is highlighted (it will turn yellow). 3. Press OK/Mute to enter the Services menu screen. MAIN MENU 1. MyLogicTM 2. Settings 3. Service orto choose, OK to select, MENU to escape Service 4. Press the ▼ button until the Configuration option is highlighted (it will turn white).
9. The first screen allows you to set the Type of cabinet. The only difference between the Type A1 and Type A2 configuration setting is that the airflow velocity limits for normal operation of the optional airflow sensor (because the Type A1 has a nominal inflow of 85 FPM, and the Type A2 is 105 FPM). If the air velocity goes out of range, the alarm will be displayed, but the cabinet will continue to run.
Air Flow Sensor Kit No. 3405500 Note: A qualified certifier must install and calibrate this sensor to obtain accurate operation. Note: Exercise caution when working on the exhaust filter cover, to prevent damaging the Exhaust HEPA filter. Installation Procedure-Units without the Ventus Canopy Connection 1. Disconnect power to the Biosafety Cabinet. 2. Loosen the two Phillips screws on the front sides of the exhaust cover, as shown 3. Tilt the exhaust cover up to access the underside of the cover. 4.
6. If you are installing the airflow sensor into a canopy connection, install the bracket onto the airflow sensor as shown. 7. Gently remove the Canopy Cable Sealing grommet, located on the top of the canopy. Remove the solid square plug. Locate the replacement plug in the air sensor kit, and push the sensor wiring harness through the slit in the plug. NOTE: The grommet and plugs are keyed – they only fit together properly when oriented as shown in the illustration.
9. Note the orientation of the sensor harness plug and the sensor; it is a keyed connection-and can only be connected in the correct orientation. Plug the sensor harness into the sensor, and the other end into the multi pin connector on the Logic+’s electronics module. 10. Reconnect the Logic to electrical service. The unit is now ready for the calibration of the air flow sensor. Note: You will need to access the certifiers menu to calibrate the airflow sensor.
9. If the password is properly entered, the first certification screen will display the blower motor’s PWM setting. 10. Press the ▲ or ▼ button to increase or decrease the blower speed as needed. When the speed is set properly, press the OK/Mute button to lock the new blower speed setting, and continue to the filter life screen. Calibration Motor Speed Adjustment The ECM setting is: 80 The current RPM is: 1050 The average RPM is: 1020 orto change motor speed, OK to select, MENU to finish 11.
Service Fixture Kit No. 3747500 Completely decontaminate all interior work surfaces of the Purifier before beginning the installation of the service valve. Additional service fixtures can be installed in any of the four available service fixture holes in the sidewalls. The service fixture kit is Labconco part number 3747500. Installation Procedure 1. Decide which of the available locations you want to install the service fixture. 2.
4. Carefully remove any remaining sealant from the service fixture hole. 5. Using the PTFE tape supplied, wrap two to three turns of tape on the male pipe thread of the valve, and the tube fitting. 6. Put the threaded end of the fixture through the hole, orienting the valve as shown in Figure 10-1. Using the silicone sealant, apply a bead of silicone on the outside surface of the cabinet side, around the valve body. This will provide a pressure tight seal around the valve body.
UV Lamp Kit No. 3858500, -01, -02 All Labconco Purifier Logic and Logic+ Series Biosafety Cabinets are pre-wired for the installation of a UV lamp kit, consisting of the UV lamp, its ballast, and fasteners. The kit is part number 3858500 for 115 Volt models, 3858501 for 100 Volt models, and 3858502 for 230 Volt units. A qualified electrician or certifier should install the UV lamp kit. Decontaminate all interior work surfaces of the Purifier before beginning the installation of the UV lamp.
5. Using the screws, flat washers and locking nuts provided, secure the UV ballast to the top of the electronics module. 6. Wire the UV ballast into the wiring harness, following the wiring diagrams located in Figure 2a-c. 7. Reattach the electronics module to the top of the cabinet before reconnecting the electrical power. 8. Raise the sash, and install the UV lamp by rotating the lamp pins into the sockets. 9.
20. The first screen allows you to set the Type of cabinet. Leave this setting alone, and press OK/Mute. 21. The second screen allows you to configure the cabinet for a canopy or not.* Leave this setting alone, and press OK/Mute. Configuration Type A Canopy Option This cabinet has: a canopy orto no canopy choose, OK to select, MENU to escape 22. This screen configures the unit for a UV light or not.
IV Bar Kit No. 3858600, -01, -02, -03 Completely decontaminate all interior work surfaces of the Purifier before beginning the installation of the IV bar. Installation Procedure 1. Disconnect power to the Logic+ and raise the sash to the fully open position. 2. Remove the four screws on the sidewalls and save them. 3. Mount one of the IV brackets on either sidewall. Orient and secure the bracket using the flat washers, lock washers and the screws as shown in Figure 1. 4.
G4 Paper Prefilter Kits Screen Prefilter Kits 34060-00, -01,-02, -03 34061-00, -01,-02, -03 The Prefilter provides a convenient means to prevent large particles from being pulled into the blower and HEPA filter of the biological safety cabinet. The Prefilter is a simple addition and easily replaced. Please note that this accessory was tested at NSF and validated to have no adverse affect on containment.
4. For 3-foot wide models only – Set the prefilter into the towel catch, ensuring the filter is captured by the long rails on the top and bottom of the towel catch. Go to Step #6. 5. For all other models - To install the kit, press bolt (6) through the towel catch frame as shown, (Note: the long flanges on the top and bottom of the towel catch go in the same direction as the bolt. Secure the bolt with lock washer (4) and hex nut (5), and tighten.
Vacu-PassTM Cord & Cable Portal Installation Note: You will need to access the right side of the cabinet in order to install the Portal Note: There must be enough clearance to pass the cord or cable between the exterior dress panel and any obstruction. Note: Some Vacu-Pass components and the cord or cable passing through it may become contaminated during use of the cabinet. Ensure all potentially contaminated components are surface decontaminated before handling or removal from the cabinet. 1.
RS-232 Connection Kits RS-232 Kit 3858310 (9 Pin), 3858311 (25 Pin) The kit contains the RS-232 PCB (P/N 3402200), the attaching hardware and connecting cables to install the PCB inside the electrical control box (located on top of the Logic+). Picture 1 shows an electrical control box with the Logic+ RS-232 PCB installed.
2) Locate the black square connecter labeled as J2 and the white connector labeled as J3 on the RS-232 PCB, see picture 3. These two connectors show through the electrical control box as shown in picture 1. Connector J2 is the RS-232 PORT connector. Connector J3 is the ALARM CONTACT connector. Also note the location of the J1 connector for later use.
4) Locate the internal RS-232 cable (P/N 3432000) included in the kit and connect it between the RS-232 PCB J1 and the Transition PCB (P/N 3431500) J6 as shown in picture 5. Picture 5 5) Re-secure the electrical control box to the top of the Logic+. 6) Connect the computer interface cable (P/N 7537800 – 9 pin or P/N 7537801 – 25 pin) included in the kit to the RS-232 PCB J2 connector, and connect the other end of this cable to a 9-pin or 25 pin serial input of a computer.
Using the RS-232 Receptacle The operation of the Logic+ Biological Safety Cabinet (BSC) can be monitored using a computer connected to the RS232 receptacle located on the top electrical box of the Logic+. The computer monitors the Logic+’s operation, but cannot control the operation of the Logic+. Connection for Computer Interface Check your computer to see which type of RS232 serial port is provided. Use one of the two connecting cables listed below: 1.
OPTIONAL LOGIC+ RS-232 DATA OUTPUT Here is the RS-232 output for the Logic+. As is standard for all Labconco units, the data is limited to 80 characters, including spaces, etc.
There are several commercially available software packages, which can read RS232 data and enter the data into a computer program such as a word processor (to create a text file) or spreadsheet (to tabulate and plot the data). Consult your laboratory supply dealer regarding the latest software available.
6. When the Logic+’s main power switch is on, the data will be transmitted and updated at the time intervals selected by the user. Logic+ Relay Contact Outputs: When equipped with the optional RS-232 contact kit board, Labconco Logic+ Biosafety Cabinet (BSC) models are provided with two (2) dry relay contacts to allow connection to an external monitoring system, or to switch other air handling units “on” when the Labconco unit is turned on.
Generally, the Labconco provided contacts can switch very low amounts of electrical current, so to control high power, line-operated devices, the Labconco contacts must be used to control yet another set of contacts that are rated for the actual load being switched. The wiring diagram indicates that the “BLOWER ON” contacts are located at J3 - pins 3 & 4 while the Airflow Alarm contacts are located at J3 - pins 1&2. Relay Contact #1 …….
The next diagram shows an example of using an AC powered coil, so the +12V supply from the Logic+ is not used. The Hasco HAT 903 relay series offers a 120VAC coil that requires only 16mA AC current as well as a 230VAC coil that draws only 9mA. The alternate circuit that uses an AC mains rated coil voltage is shown below – it does not utilize the FUSED+12V and CIRCUIT COMMON from the Labconco Logic+. Note: A W199 Magnacraft Series relay can switch up to 300Vac @ 40 Amps……….
The final diagram shows a connection for a 3-phase powered blower. In this case, a 12 VDC relay coil is used, and it gets its power from the Logic+.
Relay Contact #2……the “airflow error” contact This set of contacts (dry contacts pins 1 & 2 of J3 on the electrical enclosure, and the ORANGE wires on Labconco harness P/N 3432300) will indicate when the Logic+ has detected an airflow error, as described by the conditions below: Type of Logic+ unit All Labconco Logic+ Cabinets Alarm Condition Sash out of position LCD display message SASH TOO HIGH Airflow Error dry contacts No Response Motor RPM has shifted abruptly HEPA Filter approaching end of life—20
Section Nine – Miscellaneous Troubleshooting Refer to the following table if the Biosafety Cabinet fails to operate properly. If the suggested corrective actions do not solve the problem, contact Labconco for additional assistance. PROBLEM CAUSE CORRECTIVE ACTION Cabinet blower and lights won’t turn on Unit not plugged into outlet Plug the Biosafety Cabinet into appropriate electrical service.
PROBLEM CAUSE CORRECTIVE ACTION Blower runs slower than normal; speed control has little effect on blower speed. Blower may take more than 5 seconds to start. Motor signal wires damaged or disconnected Measure motor output signal voltage. Inspect signal wiring and connections Power Supply Board misconnected or defective Test output voltages on the Power Supply board. Motor jumper wire is damaged/ disconnected (115/100 Volt models only) Inspect grey wire #31 on 15 pin connector for continuity.
PROBLEM CAUSE CORRECTIVE ACTION Fluorescent light is dim or flickering Lamp(s) are defective Replace defective lamp(s) Lamp wiring is disconnected Inspect lamp wiring. Defective lamp ballast Replace lamp ballast. Sash is open Close sash – UV light will not work with the sash open. Lamp is defective Replace defective lamp. Lamp wiring is disconnected. Inspect lamp wiring. Defective lamp ballast Replace lamp ballast.
Contamination of work in the cabinet exhaust outlet not blocked or restricted. Blockage or restriction under the work surface Ensure that the towel catch and plenum beneath the work surface are unobstructed. Improper technique or procedure for the Biosafety Cabinet See “Use of the Cabinet” section in the manual. Restriction of the return air slots or grille – blockage of the exhaust outlet Ensure that all return air slots, grilles and the exhaust outlet are unobstructed.
Type A1 & A2 Biosafety Cabinet Replacement Parts Item 1 1A 1B 1C 2 2A 2B 2C 3 3A 3B 3C 4 4A 4B 5 Quantity 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 Part No. 3838500 3838501 3838502 3838503 3832200 3832201 3832207 3832208 3838400 3838401 3838402 3838403 9721901 9721900 9721903 1271300 Description Exhaust HEPA Filter 3-ft Exhaust HEPA Filter 4-ft Exhaust HEPA Filter 5-ft Exhaust HEPA Filter 6-ft Motor / Blower Assembly, 3 Ft. Motor / Blower Assembly, 4 Ft. Motor / Blower Assembly, 5 Ft.
Type B2 Biosafety Cabinet Replacement Parts Item Quantity Part No. 1 1A 2 2A 3 3A 4 4A 5 1 1 1 1 1 1 2 2 1 3438501 3438503 3832209 3832210 3838401 3838403 9721900 9721903 1271300 Description Exhaust HEPA Filter 4-ft Exhaust HEPA Filter 6-ft Motor / Blower Assembly, 4 Ft. TE Motor / Blower Assembly, 6 Ft.
Dimensions 172 Product Service 1-800-522-7658