Quick Start Guide

28 C Series Quick Start Guide 29
C 28:4
Level Load Rated power
Line Current *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o via NomadLink 0 0 0 0 0
Powered on, idling. 123 0 123 420 106
Amp (I) Watt
Pink noise
(⁄ rated power)
8Ω / Ch. 700 x 4
11.6 5.8 727 350 377 1286 324
16Ω / Bridged 1400 x 2
4Ω / Ch. 700 x 4
13.0 6.5 775 350 425 1450 365
8Ω / Bridged 1400 x 2
2Ω / Ch. 300 x 4
9.4 4.7 529 150 379 1293 326
4Ω / Bridged 600 x 2
100V / Ch. 700 x 4
10.4 5.2 663 350 313 1068 269
200V / Bridged 1400 x 2
Pink noise
(¼ rated power)
*3)
8Ω / Ch. 700 x 4
24.0 12.0 1589 933 656 2237 564
16Ω / Bridged 1400 x 2
4Ω / Ch. 700 x 4
20.8 10.4 1359 700 659 2249 567
8Ω / Bridged 1400 x 2
4Ω / Ch. 300 x 4
14.0 7.0 843 300 543 1853 467
8Ω / Bridged 600 x 2
100V / Ch. 700 x 4
21.4 10.7 1458 933 525 1790 451
200V / Bridged 1400 x 2
Mains connector, 230V CE version 16 A, CEE7
Mains connector, 115V ETL version 20 A / 5-20P
*1) The amplier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specied here is what
is known as the “Active Power” in the amplier providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw gures measured at 230V. 115V gures are 230V gures multiplied by two.
*3) Figures measured at maximum power before amplier protection and limiter features are engaged. Typically this is between ¼ and ⁄ of rated power. Note that
the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess
of max. ratings.
C 16:4
Level Load Rated power
Line Current *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o via NomadLink 0 0 0 0 0
Powered on, idling. 129 0 129 440 111
Amp (I) Watt
Pink noise
(⁄ rated power)
8Ω / Ch. 400 x 4
8.6 4.3 526 200 326 1112 280
16Ω / Bridged 800 x 2
4Ω / Ch. 300 x 4
8.2 4.1 485 150 335 1143 288
8Ω / Bridged 600 x 2
2Ω / Ch. n.r.
4Ω / Bridged n.r.
100V / Ch. 400 x 4
7.6 3.8 463 200 263 897 226
200V / Bridged 800 x 2
Pink noise
(¼ rated power)
*3)
8Ω / Ch. 400 x 4
16.2 8.1 1046 533 513 1749 441
16Ω / Bridged 800 x 2
4Ω / Ch. 300 x 4
15.2 7.6 953 400 553 1887 475
8Ω / Bridged 600 x 2
2Ω / Ch. n.r.
4Ω / Bridged n.r.
100V / Ch. 400 x 4
14.4 7.2 944 533 411 1401 353
200V / Bridged 800 x 2
Mains connector, 230V CE version 16 A, CEE7
Mains connector, 115V ETL version 15 A / 5-15P
*1) The amplier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specied here is what
is known as the “Active Power” in the amplier providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw gures measured at 230V. 115V gures are 230V gures multiplied by two.
*3) Figures measured at maximum power before amplier protection and limiter features are engaged. Typically this is between ¼ and ⁄ of rated power. Note that
the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess
of max. ratings.