Appendix 1 - Error Codes (continued)
Code Description L or H Procedure
108 Flame lost in run L 1. Check main valve wiring and operation - correct any
errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, ame detector,
ame detector siting or ame rod position.
5. If steps 1 through 4 are correct and the fault persists,
replace the module.
109 Ignition failed L 1. Check main valve wiring and operation - correct any
errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, ame detector,
ame detector siting or ame rod position.
5. If steps 1 through 4 are correct and the fault persists,
replace the module.
110 Ignition failure occurred H Hold time of recycle and hold option. Will not be a
lockout fault. Hold only. Internal hardware test. Not a
lockout.
111 Flame current lower than weak threshold H Hold time of recycle and hold option. Will not be a
lockout fault. Hold only. Internal hardware test. Not a
lockout.
113 Flame circuit timeout L Flame sensed during initiate or off cycle, hold 240 sec-
onds, if present after 240 seconds, system will lockout.
119 Control Interaction fault H Flap valve identications congured incorrectly.
122 Lightoff rate proving failed L 1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to
change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
123 Purge rate proving failed L 1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to
change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
128 Fan speed failed during prepurge H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFD’s (Variable-speed Fan Drive) ability
to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
App1
cont.