Service Manual NeoTherm 80 - NeoTherm 285
Appendix 1 - Error Codes (continued)
Code Description L or H Procedure
97 Internal fault: A2D mismatch. L Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
98 Internal fault: Exceeded VSNSR voltage
tolerance
L Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
99 Internal fault: Exceeded 28V voltage toler-
ance
L Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
100 Pressure sensor fault H 1. Verify the pressure sensor is a 4-20 ma source.
2. Check wiring and correct any possible errors.
3. Test the pressure sensor for correct operation.
4. Replace the pressure sensor.
5. If previous steps are correct and fault persists, re-
place the module.
105 Flame detected out of sequence H or L 1. Check that ame is not present in the combustion
chamber. Correct any errors.
2. Make sure that the ame detector is wired to the cor-
rect terminal.
3. Make sure the ame and ground wires are protected
from stray noise pickup.
4. Reset and sequence the module, if code reappears,
replace the ame detector.
5. Reset and sequence the module, if code reappears,
replace the module.
106 Flame lost in MFEP (Main Flame Establish-
ing Period)
L 1. Check main valve wiring and operation - correct any
errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, ame detector,
ame detector siting and ame rod position.
5. If steps 1 through 4 are correct and the fault persists,
replace the module.
107 Flame lost early in run L 1. Check main valve wiring and operation - correct any
errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, ame detector,
ame detector siting or ame rod position.
5. If steps 1 through 4 are correct and the fault persists,
replace the module.
App1
cont.