User Guide
81
Service Manual NeoTherm 80 - NeoTherm 285
App1
Appendix 1 - Error Codes
This table includes a listing of the faults that might be generated by the controllers, and displayed on the Operator Interface. Some
of these can be corrected by an installer changing a parameter, while other conditions are more complicated, and will require a
service technician.
The rst column lists the code number that will appear at the beginning of the Lockout or Hold message in the orange bar at
the bottom of the screen. The second column lists the text as it will appear on the Operator Interface. The third column shows
whether the condition will cause a Hold, or Lockout, or both. The fourth column lists some suggestions for corrective action.
Code Description L or H Procedure
1 Uncongured safety data L 1. New device, complete device conguration and
safety verication.
2. If fault repeats, replace module.
2 Waiting for safety
data verication
L 1. Device in Conguration mode and safety parameters
need verication and a device needs reset to complete
verication.
2. Conguration ended without verication, re- enter
conguration, verify safety parameters and reset device
to complete verication.
3. If fault repeats, replace module.
3 Internal fault:
Hardware fault
H Internal fault
1. Reset module
2. If fault repeats, replace module.
4 Internal fault:
Safety relay key feedback error
H Internal fault
1. Reset module
2. If fault repeats, replace module.
5 Internal fault:
Unstable power (DC) output
H Internal fault
1. Reset module
2. If fault repeats, replace module.
6 Internal fault:
Invalid processor clock
H Internal fault
1. Reset module
2. If fault repeats, replace module.
7 Internal fault:
Safety relay drive error
H Internal fault
1. Reset module
2. If fault repeats, replace module.
8 Internal fault:
Zero crossing not detected
H Internal fault
1. Reset module
2. If fault repeats, replace module.
9 Internal fault:
Flame bias out of range
H Internal fault
1. Reset module
2. If fault repeats, replace module.
10 Internal fault:
Invalid burner control state
L Internal fault
1. Reset module
2. If fault repeats, replace module.