User Guide

72
Service Manual NeoTherm 80 - NeoTherm 285
QuickStart Thismenugivesyouaneasywaytocheckorchangethemostcommonset-
tings on the unit:
•CHsetpoint
•DHWsetpoint
•Outdoorreset(Note-Youcannotdisablethisfunctionfromtheinterface)
•Lowwatertemperature
•Maximumoutdoortemperature
•Minimumoutdoortemperature
•Adjustablehighlimit
•Adjustablelowlimit
Login Ifyouwanttochangeasetupvalueorfunction,andthesystemrequiresa
password,youcanenterithere.
Test Theseparametersletyousettheburneroperationforcombustiontesting,and
control pump operation.
AdvancedSetup Thesub-menuslistedhereallowyoutosetupmostofthefunctionsonthe
controller.(Formanyofthesefunctions,thesystemwillrequireapassword
beforeitwillallowyoutomakechanges.)
Diagnostics UsetheDiagnosticstocheckthestatusofthesensorsandthedigitalinputs
andoutputs.Thesystemalsorecordsahistoryoflockoutsandalarms.
DisplaySetup Youcanusethisoptiontoadjustthecontrastofthedisplayorchangethe
itemswhichappearatthetopoftheHomedisplay.
Table D5-2 - Functions on Info/ Install Menu
Changing a Value
Theprocedureforchangingacontrolvalueusedbythe
systemislistedbelow.(Inthisexample,wewillusethe
screenfortheCHSetpoint.)
• UsetheUp-andDown-Arrowbuttonstostepdown
throughthelistuntilyouhavehighlightedthecorrect
lineonthedisplay.
• PresstheroundOKbuttontoselectthatline.Figure
D5-4showsatypicalscreenforthistypeofsetting.
• Thecurrentsettingforthesetpointappearsinthe
boxatthetopofthescreen.Inthisexample,thisis
182°F.
• Thenumbersneartheleftedgeofthescreenshow
theallowablerangeforthisvalue.Inthiscase,the
setpointcanbesetanywherebetween190°Fand
55°F.
• PresstheUp-andDown-Arrowbuttonstoscrollthe
setpointuntilyouseethecorrectvalueinthebox.
• Whenthevalueiscorrect,presstheroundOKbutton.
Fig. D5-4 – Changing a value
Using the Current User Interface - continued
D5