2. Once you have completed the high re combustion test, measure the CO
2
/
O
2
in the ue products at Low Fire.
How to get there: Use the Down arrow to set the “Rate” to “20%.” The NT
unit is now forced to low re mode for 5 minutes.
The CO
2
readings should be between the values shown in Table C2-1. If
the CO
2
is not within the range shown, adjustments may be made. To adjust
the low re CO
2
, locate the low re adjuster screw as shown in Fig. C2-1.
Slowly make adjustments in 1/16 of a revolution increments until the CO
2
is within the range identied. For the low re adjustment, turning the screw
clockwise (CW) opens the adjustment and makes the mixture richer.
3. Repeat steps 2 and 3 to conrm that the CO
2
readings are within the re-
quired ranges. Adjust each setting again if necessary.
4. Conrm that the differential pressure is still within the appropriate range.
5. If any of the measurements cannot be adjusted to the specied ranges or
the CO levels are above 150 ppm when adjusted, see Section C4, “Trouble-
shooting Combustion Problems.”
6. Remove the differential pressure gauge from the air and gas pressure taps
making sure to close all ports after the gauge has been removed.
Combustion Adjustment Procedure -
Units with Original (White) User Interface - continued
C2
cont.