User Guide

36
Service Manual NeoTherm 80 - NeoTherm 285
Checking the Blower
B18
Yes
Blower goes
to full speed?
Replace the SOLA controller
See Section D8, D9.
Unplug J2. This is the
control signal to the blower.
No
Yes
Check wiring
harness. Wires
OK?
No
Replace wire harness
No
Has call for heat?
At start of test, unit should be ready to run (”Standby”)
Blower runs
Problem with temp. sensor(s)
System sensor - Section B22
DHW sensor - Section B23
Short contacts
for call for heat:
CH: TB7 5-6
DHW: TB6 5-6
Blower does not run
Bad blower. Replace the blower.
See Section B19.