Service Manual NeoTherm 80 - NeoTherm 285
Checking the Air Pressure Switch - Blower Proving Switch
Exhaust vent
blocked?
Yes
No
Clear the vents.
Check the bird screens
or terminals.
Check for blocked air intake
and exhaust vents.
Clean with a shop-vac.
Dirty fan?
Yes
No
Test the air pressure switch.
(See Section B16.)
Switch is OK?
No
Replace switch.
Yes
Problem with
blower?
Yes
See Section B18 -
“Checking the Blower”
No
Heat exchanger
is plugged?
Yes
Clean the heat
exchanger.
See Section C5.
B15