Appendix 1 - Error Codes (continued)
Code Description L or H Procedure
232 Invalid pressure sensor type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
234 Invalid outlet high limit enable setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
235 Invalid outlet connector type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
236 Invalid inlet connector type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
237 Invalid DHW (Domestic Hot Water) connec-
tor type setting
L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
238 Invalid stack connector type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
239 Invalid header connector type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
240 Invalid outdoor connector type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.