Service Manual NeoTherm 80 - NeoTherm 285
Appendix 1 - Error Codes (continued)
Code Description L or H Procedure
196 Invalid ignition source setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
197 Invalid interlock open response setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
198 Invalid interlock start check setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
199 Invalid LCI (Limit Control Input) enable set-
ting
L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
200 Invalid lightoff rate setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
201 Invalid lightoff rate proving setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
202 Invalid MFEP (Main Flame Establishing
Period) time setting
L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
203 Invalid MFEP (Main Flame Establishing
Period) ame failure response setting
L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
204 Invalid NTC sensor type setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
205 Invalid outlet high limit response setting L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
207 Invalid PII (Pre-Ignition Interlock) enable
setting
L 1. Return to conguration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
App1
cont.