Install Instructions
Table Of Contents
- Cover
- Table of Contents
- Table of Contents, Page 2
- Section 1 -GENERAL INFORMATION
- Section 2 -LOCATING THE APPLIANCE
- Section 3 -VENTING AND COMBUSTION AIR
- Section 4 -GAS SUPPLY AND PIPING
- Section 5 -PUMP REQUIREMENTS
- Section 6 -WATER CONNECTIONS -NTH BOILER
- Section 7 -ELECTRICAL AND WIRING DIAGRAMS
- Section 8 -THE USER INTERFACE
- 8.1 About the User Interface
- 8.2 Navigating the User Interface
- 8.3 The Home Display
- 8.4 Customizing your Home Display
- 8.5 Entering/Changing Control Settings
- 8.6 Quick Start
- Configuration and Setup
- 8.7 24 VAC Transformerwith Integral Circuit Breaker
- 8.8 Hydronic Heating Demand
- 8.9 Anti-Short-Cycle (ASC)
- 8.10 Outdoor Air Temperature Sensor
- 8.11 Outdoor Reset
- 8.12 Warm Weather Shutdown
- 8.13 Domestic Hot Water
- 8.14 About Lead Lag Operation
- 8.15 Adjusting CO2
- Section 9 -FIRST START-UP AND ADJUSTMENTINSTRUCTIONS
- Section 10 -MAINTENANCE
- Section 11 -OPERATING DETAILS AND TROUBLESHOOTING
- Section 12 -REPLACEMENT PARTS
- Appendix A -SOFTWARE CONTROL FUNCTIONS. Next 5 pages
- Appendix B -ERROR MESSAGES. Next 8 pages
- Back Cover. Contact information. Product and Service Videos
Page 69
NEOTHERM Residential Boilers
80 DHW (Domestic Hot Water) high limit H or L 1. Check wiring and correct any possible errors.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists, replace the
module.
81 Delta T limit H or L 1. Check inlet and outlet sensors and pump circuits for proper
operation.
2. Recheck the Delta T Limit to conrm proper setting.
3. If previous steps are correct and fault persists, replace the
module.
82 Stack limit H or L 1. Check wiring and correct any possible errors.
2. Replace the Stack high limit.
3. If previous steps are correct and fault persists, replace the
module.
91 Inlet sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists, replace the
module.
92 Outlet sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the Outlet sensor.
3. If previous steps are correct and fault persists, replace the
module.
93 DHW (Domestic Hot Water) sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists, replace the
module.
94 Header sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace the
module.
95 Stack sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace the
module.
96 Outdoor sensor fault H 1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace the
module.
97 Internal Fault: A2D mismatch. L Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
98 Internal Fault: Exceeded VSNSR voltage
tolerance
L
99 Internal Fault: Exceeded 28V voltage
tolerance
L
100 Pressure Sensor Fault H 1. Verify the pressure sensor is a 4-20 mA source.
2. Check wiring and correct any possible errors.
3. Test the pressure sensor for correct operation.
4. Replace the pressure sensor.
5. If previous steps are correct and fault persists, replace the
module.