Install Instructions
Table Of Contents
- Cover
- Table of Contents
- Table of Contents, Page 2
- Section 1 -GENERAL INFORMATION
- Section 2 -LOCATING THE APPLIANCE
- Section 3 -VENTING AND COMBUSTION AIR
- Section 4 -GAS SUPPLY AND PIPING
- Section 5 -PUMP REQUIREMENTS
- Section 6 -WATER CONNECTIONS -NTH BOILER
- Section 7 -ELECTRICAL AND WIRING DIAGRAMS
- Section 8 -THE USER INTERFACE
- 8.1 About the User Interface
- 8.2 Navigating the User Interface
- 8.3 The Home Display
- 8.4 Customizing your Home Display
- 8.5 Entering/Changing Control Settings
- 8.6 Quick Start
- Configuration and Setup
- 8.7 24 VAC Transformerwith Integral Circuit Breaker
- 8.8 Hydronic Heating Demand
- 8.9 Anti-Short-Cycle (ASC)
- 8.10 Outdoor Air Temperature Sensor
- 8.11 Outdoor Reset
- 8.12 Warm Weather Shutdown
- 8.13 Domestic Hot Water
- 8.14 About Lead Lag Operation
- 8.15 Adjusting CO2
- Section 9 -FIRST START-UP AND ADJUSTMENTINSTRUCTIONS
- Section 10 -MAINTENANCE
- Section 11 -OPERATING DETAILS AND TROUBLESHOOTING
- Section 12 -REPLACEMENT PARTS
- Appendix A -SOFTWARE CONTROL FUNCTIONS. Next 5 pages
- Appendix B -ERROR MESSAGES. Next 8 pages
- Back Cover. Contact information. Product and Service Videos
Page 67
NEOTHERM Residential Boilers
17 Internal fault:
Safety relay test failed due to safety relay
not OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
18 Internal fault:
Safety relay test failed due to feedback
not ON
L
19 Internal fault:
Safety RAM write
L
20 Internal fault:
Internal fault: Flame ripple and overow
H
21 Internal fault:
Flame number of sample mismatch
H
22 Internal fault:
Flame bias out of range
H
23 Internal fault:
Bias changed since heating cycle starts
H
24 Internal fault:
Spark voltage stuck low or high
H
25 Internal fault:
Spark voltage changed too much during
ame sensing time
H
26 Internal fault:
Static ame ripple
H
27 Internal fault:
Flame rod shorted to ground detected
H
28 Internal fault:
A/D linearity test fails
H
29 Internal fault:
Flame bias cannot be set in range
H
30 Internal fault:
Flame bias shorted to adjacent pin
H
31 Internal fault:
SLO electronics unknown error
H
32-46 Internal fault:
Safety Key 0 through 14
L
47 Flame Rod to ground leakage H
48 Static ame (not ickering) H
49 24 VAC voltage low/high H 1. Check the module and display connections.
2. Check the module power supply and make sure that
frequency, voltage and VA meet the specications.
50 Modulation fault H Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
Internal sub-system fault.
51 Pump fault H
52 Motor tachometer fault H