Install Instructions
Table Of Contents
- Cover
- Table of Contents
- Table of Contents, Page 2
- Section 1 -GENERAL INFORMATION
- Section 2 -LOCATING THE APPLIANCE
- Section 3 -VENTING AND COMBUSTION AIR
- Section 4 -GAS SUPPLY AND PIPING
- Section 5 -PUMP REQUIREMENTS
- Section 6 -WATER CONNECTIONS -NTH BOILER
- Section 7 -ELECTRICAL AND WIRING DIAGRAMS
- Section 8 -THE USER INTERFACE
- 8.1 About the User Interface
- 8.2 Navigating the User Interface
- 8.3 The Home Display
- 8.4 Customizing your Home Display
- 8.5 Entering/Changing Control Settings
- 8.6 Quick Start
- Configuration and Setup
- 8.7 24 VAC Transformerwith Integral Circuit Breaker
- 8.8 Hydronic Heating Demand
- 8.9 Anti-Short-Cycle (ASC)
- 8.10 Outdoor Air Temperature Sensor
- 8.11 Outdoor Reset
- 8.12 Warm Weather Shutdown
- 8.13 Domestic Hot Water
- 8.14 About Lead Lag Operation
- 8.15 Adjusting CO2
- Section 9 -FIRST START-UP AND ADJUSTMENTINSTRUCTIONS
- Section 10 -MAINTENANCE
- Section 11 -OPERATING DETAILS AND TROUBLESHOOTING
- Section 12 -REPLACEMENT PARTS
- Appendix A -SOFTWARE CONTROL FUNCTIONS. Next 5 pages
- Appendix B -ERROR MESSAGES. Next 8 pages
- Back Cover. Contact information. Product and Service Videos
Page 65
NEOTHERM Residential Boilers
Name PW? Function How to get there
Pump exercise interval Y The system can be set to exercise the pumps at
set intervals. Enter a non-zero value to turn on the
function.
Info/ Advanced Setup/ System
Cong./ Pump Cong.
Pump exercise time Y If the pump exercise feature is enabled, this value
sets the length of time that each pump will be
exercised.
Info/ Advanced Setup/ System
Cong./ Pump Cong.
Set high re Y This is used during combustion setup to set the
“high re” condition.
Info/ Test/ Forced Rate
Set low re Y This is used during combustion setup to set the “low
re” condition.
Info/ Test/ Forced Rate
Setpoint (LL) - When using the Lead/ Lag system to control
multiple boilers –
This setpoint is used to control the hydronic (Central
Heat) function.
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
Setpoint source (CH) Y Set to “Local.” Info/ Advanced Setup/ CH
Conguration
Setpoint source (LL) Y When using the Lead/ Lag system to control
multiple boilers –
Set to “Local.”
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
Follower enable (LL) - When using the Lead/ Lag system to control
multiple boilers –
One of the controllers must be set up as the Lead
Lag Master to supervise the Lead Lag system.
The controllers on all of the other boilers must be
enabled as Followers. See the section on “About
Lead Lag.”
The choices are: Disable/ Enable via Modbus
Master/ Enable via SOLA Master
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Follower Cong.
Follower mode (LL) Y When using the Lead/ Lag system to control
multiple boilers –
Set to “Equal Run Time.”
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Follower Cong.
Start test Y This is used during combustion setup to start the
test ring.
Info/ Test
System pump control Y The System pump can be turned on manually, or it
can be set to operate automatically.
Info/ Test/ Manual Pump Operation
Info/ Advanced Setup/ System
Cong./ Pump Cong.
System pump overrun
time
Y This indicates how long the System pump will
remain on after demand from any source ends.
Info/ Advanced Setup/ System
Cong./ Pump Cong.
Temperature units - Fahrenheit or Celsius Info/ Advanced Setup/ System
Cong./ System Cong.
Warm weather shutdown Y The system can be set to shut down if the outdoor
temperature rises above a certain value.
Info/ Advanced Setup/ CH
Conguration/ Warm Weather
Shutdown
Warm weather shutdown
setpoint
- If warm weather shutdown is enabled –
If the outdoor temperature is higher than this value,
the system will be shut off for Central Heating
functions.
Info/ Advanced Setup/ CH
Conguration/ Warm Weather
Shutdown