Install Instructions
Table Of Contents
- Cover
- Table of Contents
- Table of Contents, Page 2
- Section 1 -GENERAL INFORMATION
- Section 2 -LOCATING THE APPLIANCE
- Section 3 -VENTING AND COMBUSTION AIR
- Section 4 -GAS SUPPLY AND PIPING
- Section 5 -PUMP REQUIREMENTS
- Section 6 -WATER CONNECTIONS -NTH BOILER
- Section 7 -ELECTRICAL AND WIRING DIAGRAMS
- Section 8 -THE USER INTERFACE
- 8.1 About the User Interface
- 8.2 Navigating the User Interface
- 8.3 The Home Display
- 8.4 Customizing your Home Display
- 8.5 Entering/Changing Control Settings
- 8.6 Quick Start
- Configuration and Setup
- 8.7 24 VAC Transformerwith Integral Circuit Breaker
- 8.8 Hydronic Heating Demand
- 8.9 Anti-Short-Cycle (ASC)
- 8.10 Outdoor Air Temperature Sensor
- 8.11 Outdoor Reset
- 8.12 Warm Weather Shutdown
- 8.13 Domestic Hot Water
- 8.14 About Lead Lag Operation
- 8.15 Adjusting CO2
- Section 9 -FIRST START-UP AND ADJUSTMENTINSTRUCTIONS
- Section 10 -MAINTENANCE
- Section 11 -OPERATING DETAILS AND TROUBLESHOOTING
- Section 12 -REPLACEMENT PARTS
- Appendix A -SOFTWARE CONTROL FUNCTIONS. Next 5 pages
- Appendix B -ERROR MESSAGES. Next 8 pages
- Back Cover. Contact information. Product and Service Videos
Page 64
LAARS Heating Systems
Name PW? Function How to get there
Off hysteresis (DHW) - When producing Domestic Hot Water –
The control system will not shut off the boiler until
the temperature at the System sensor rises to the
DHW setpoint plus a hysteresis value (normally
about 10°F).
Info/ Advanced Setup/ DHW
Conguration
Off hysteresis (LL) - When using the Lead/ Lag system to control
multiple boilers –
The control system will not shut off the boilers until
the temperature at the System sensor rises to
the Lead Lag CH setpoint plus a hysteresis value
(normally about 10°F).
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
On hysteresis (CH) - For hydronic heating (Central Heat) –
The control system will not re the boiler until the
temperature at the System sensor drops to the CH
setpoint minus a hysteresis value (normally about
10°F).
Info/ Advanced Setup/ CH
Conguration
On hysteresis (DHW) - When producing Domestic Hot Water –
The control system will not re the boiler until the
temperature at the System sensor drops to the
DHW setpoint minus a hysteresis value (normally
about 10°F).
Info/ Advanced Setup/ DHW
Conguration
On hysteresis (LL) - When using the Lead/ Lag system to control
multiple boilers –
The control system will not re the boilers until the
temperature at the System sensor drops to the Lead
Lag CH setpoint minus a hysteresis value (normally
about 10°F).
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
Outdoor reset (CH) - Enable = Outdoor Reset feature turned on Quick Start
Info/ Advanced Setup/ CH
Conguration/ Outdoor Reset Cong.
Outdoor reset enable
(LL)
- When using the Lead/ Lag system to control
multiple boilers –
Enable = Outdoor Reset feature turned on
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Outdoor Reset
P gain (CH) Y This gain is applied to the Proportional term of the
PID equation for the hydronic (Central Heat) loop.
Info/ Advanced Setup/ CH
Conguration
P gain (DHW) Y This gain is applied to the Proportional term of the
PID equation for the Domestic Hot Water loop.
Info/ Advanced Setup/ DHW
Conguration
P gain (LL) Y When using the Lead/ Lag system to control
multiple boilers –
This gain is applied to the Proportional term of the
PID equation for the hydronic loop.
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
Priority time Y If this parameter is non-zero, then a Domestic Hot
Water demand takes priority over other demand
sources for the specied time. The priority override
timing is reset when demand from the DHW source
turns off.
Info/ Advanced Setup/ DHW
Conguration
Priority vs Central Heat Y If a CH call and a DHW call arrive at the same time,
which has priority?
Info/ Advanced Setup/ DHW
Conguration
Priority vs Lead Lag Y When using the Lead/ Lag system to control
multiple boilers –
If a call for hydronic heat and a DHW call arrive at
the same time, which has priority?
Info/ Advanced Setup/ DHW
Conguration