Install Instructions
Table Of Contents
- Cover
- Table of Contents
- Table of Contents, Page 2
- Section 1 -GENERAL INFORMATION
- Section 2 -LOCATING THE APPLIANCE
- Section 3 -VENTING AND COMBUSTION AIR
- Section 4 -GAS SUPPLY AND PIPING
- Section 5 -PUMP REQUIREMENTS
- Section 6 -WATER CONNECTIONS -NTH BOILER
- Section 7 -ELECTRICAL AND WIRING DIAGRAMS
- Section 8 -THE USER INTERFACE
- 8.1 About the User Interface
- 8.2 Navigating the User Interface
- 8.3 The Home Display
- 8.4 Customizing your Home Display
- 8.5 Entering/Changing Control Settings
- 8.6 Quick Start
- Configuration and Setup
- 8.7 24 VAC Transformerwith Integral Circuit Breaker
- 8.8 Hydronic Heating Demand
- 8.9 Anti-Short-Cycle (ASC)
- 8.10 Outdoor Air Temperature Sensor
- 8.11 Outdoor Reset
- 8.12 Warm Weather Shutdown
- 8.13 Domestic Hot Water
- 8.14 About Lead Lag Operation
- 8.15 Adjusting CO2
- Section 9 -FIRST START-UP AND ADJUSTMENTINSTRUCTIONS
- Section 10 -MAINTENANCE
- Section 11 -OPERATING DETAILS AND TROUBLESHOOTING
- Section 12 -REPLACEMENT PARTS
- Appendix A -SOFTWARE CONTROL FUNCTIONS. Next 5 pages
- Appendix B -ERROR MESSAGES. Next 8 pages
- Back Cover. Contact information. Product and Service Videos
Page 61
NEOTHERM Residential Boilers
Appendix A -
SOFTWARE CONTROL FUNCTIONS
This table includes a listing of all of the control functions that can be used by the operator or installer. Functions that
require a password are indicated in the second column.
Name PW? Function How to get there
Adjustable high limit Y The absolute high limit for the water outlet is pre-set
at the factory. If desired, you can set a lower value
here.
Quick Start
Adjustable stack limit Y The absolute high limit for the stack temperature
is pre-set at the factory. If desired, you can set a
lower value here.
Quick Start
Alert log - This displays the 15 most recent alerts. Info/ Diagnostics/ History
Analog sensors - This shows the current condition of selected
sensors – temperatures, fan speed, ame signal,
etc.
Info/ Diagnostics
Anti short-cycle time - This feature can be set to prevent the burner from
ring and then shutting off quickly in response to a
call for heat that changes state quickly.
Info/ Advanced Setup/ System
Cong./ System Cong.
Base load common rate
(LL)
- When using the Lead/ Lag system to control
multiple boilers –
As the heating load increases, this value sets the
point where the controller will re the next boiler.
See the section on “About Lead/ Lag.”
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.
Boiler pump control Y The boiler pump can be turned on manually, or it
can be set to operate automatically.
Info/ Test/ Manual Pump Operation
Info/ Advanced Setup/ System
Cong./ Pump Cong.
Boiler pump cycle count Y A new value can be written here if the pump or
controller is replaced.
Info/ Advanced Setup/ System
Cong./ Statistics Cong.
Boiler pump overrun
time
Y This indicates how long the boiler pump will remain
on after demand from any source ends.
Info/ Advanced Setup/ System
Cong./ Pump Cong.
Burner cycle count Y This is incremented on each entry to Run. A new
value can be written here if the burner or controller
is replaced.
Info/ Advanced Setup/ System
Cong./ Statistics Cong.
Burner name Y This parameter allows the installer to give each
boiler unit a unique name.
Info/ Advanced Setup/ System
Cong./ System ID and Access
Burner off inhibit time Y Set to “No Value.” Info/ Advanced Setup/ System
Cong./ System Cong.
Burner run time Y This measures the time spent in the Run state.
A new value can be written here if the burner or
controller is replaced.
Info/ Advanced Setup/ System
Cong./ Statistics Cong.
CH setpoint - This setpoint is used to control the hydronic (Central
Heat) function.
Quick Start
Info/ Advanced Setup/ CH
Conguration
D gain (CH) Y This gain is applied to the Differential term of the
PID equation for the CH loop.
Info/ Advanced Setup/ CH
Conguration
D gain (DHW) Y This gain is applied to the Differential term of the
PID equation for the DHW loop.
Info/ Advanced Setup/ DHW
Conguration
D gain (LL) Y When using the Lead/ Lag system to control
multiple boilers –
This gain is applied to the Differential term of the
PID equation for the hydronic heating loop.
Info/ Advanced Setup/ Lead Lag
Conguration/ LL Master Cong.










