Install Instructions

Table Of Contents
Page 25
NEOTHERM Residential Boilers
Figure 16. -ControlPanelLayout
7.5 OptionalFieldConnections
Terminal block 8 (TB8) in the control panel is used for the
‘Safety Chain’ and for connecting optional components such
as low water cutoffs, ow switches, additional high limits, and
other eld-supplied devices that must be interlocked with the
boiler. These are non-powered dry contacts only. All safeties
or end switches must be wired in series by removing the
supplied jumpers.
See Figure 16
7.4 HydronicHeatingUsingExternal
ModulationControl
About External Control -
When the NeoTherm is used for hydronic heating with
external modulation control, a call for heat must be supplied
to the “T-T or Interlock” terminal. Once the call is supplied
the control starts the Boiler and System pumps and begins the
ignition process. Once in Run, the NeoTherm monitors the
ame signal, call for heat, safeties, and water temperatures.
The boiler setpoint is used to limit the maximum water
temperature leaving the boiler only. The modulation rate
is controlled by a 4-20mA signal supplied by an external
control. (This can also be 0-10Vdc using a converter - Laars
part number CA006100.) When setting up a system using an
external control, take care to set Anti-Short Cycle feature to
prevent “hunting “ and possible premature component failure.