Install Instructions

Table Of Contents
Page 16
LAARS Heating Systems
6.3CondensateDrain
A condensate drain trap is built into the NeoTherm unit.
Connect a 3/4” PVC pipe between the drain connection and
a oor drain (or a condensate pump if a oor drain is not
accessible).
The condensate drain must be installed so as to prevent
accumulation of condensate. When a condensate pump is not
used, the tubing must continuously slope downward toward
the drain with no spiraling.
Consult local codes for the proper disposal method for the
condensate.
Caution
Condensate is mildly acidic (pH = 5), and may harm
some oor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe,
and anything that will come in contact with the
condensate can withstand the acidity, or neutralize
the condensate before disposal. Damagecausedby
failuretoinstallaneutralizerkitortoadequately
treatcondensatewillnotbethemanufacturers
responsibility.
6.4 Freeze Protection
NeoTherm units are certied for indoor use only, and are not
design-certied for placement outdoors.
Proper precautions for freeze protection are recommended
for boiler installations in areas where the danger of freezing
exists.
Power outage, interruption of gas supply, failure of system
components, activation of safety devices, etc., may prevent a
boiler from ring. Any time a boiler is subjected to freezing
conditions, and the boiler is not able to re, and/or the
water is not able to circulate, there is a risk of freezing
in the boiler or in the pipes in the system. When water
freezes, it expands which may result in bursting of pipes, or
damage to the boiler, which could result in leaking or ooding
conditions.
Do not use automotive antifreeze. To help prevent freezing,
Laars recommends the use of inhibited glycol concentrations
between 20% and 35% glycol. Typically, this concentration
will serve as burst protection for temperatures down to
approximately -5°F (-20°C). If temperatures are expected to
be lower than -5°F (-20°C), glycol concentrations up to 50%
can be used. When concentrations greater than 35% are used,
water ow rates must be increased to maintain a 20°F to 25°F
temperature rise through the boiler.
NOTE: Laars supplied pumps are not all capable of
maintaining the reduced temperature rise required
with glycol concentrations greater than 35%. If glycol
concentrations required are greater than 35% a eld
supplied pump should be used.
Caution
Different glycol products may provide varying degrees of
protection. Glycol products must be maintained properly
in a heating system, or they may become ineffective.
Consult the glycol specications, or the glycol
manufacturer, for information about specic products,
maintenance of solutions, and set up according to your
particular conditions.
6.5NTHSuggestedPipingSchematics
Figure 9 through Figure 15 shows suggested piping
congurations for NTH boilers. These diagrams are only
meant as a guide. All components or piping required by local
code must be installed.
6.6RecognizedChemicals
The following manufacturers offer glycols, inhibitors, and
anti foamants that are suitable for use in the NeoTherm.
Please refer to the manufacturers instructions for proper
selection and application.
1. Sentinel Performance Solutions Group
2. Hercules Chemical Company
3. Dow Chemical Company