Instruction Manual

Page 6
LAARS Heating Systems
Step 3 SET UP MODE, CONTINUED
LBT: Stands for Low Boiler Temperature.
This is the
low boiler set point used for outdoor reset.
Example: on a 65 degree day you may only need 120 degree boiler supply temperature.
With the LBT, HOD,LOD screen ON, press the NEXT button
Use the up or down arrows to select the desired low boiler temperature, LBT
Press NEXT.
HOD will appear on the screen.
HOD: This is the high outdoor set point used for outdoor reset.
Use the up or down arrows to select the desired
high outdoor temperature (HOD),
Page 6