Instruction Manual
Page 3
Mascot II
Step 2
DHW SET POINT
The DHW set point is the Domestic Hot Water set point.
If using DHW, follow this step. Otherwise move to step 3.
It is recommended on the Mascot II that a mixing valve be used. When using a mixing valve we
recommend the DHW be set at 150 degrees. Mix supply temperature per local code requirements. .
• Starting in the outlet screen, you will see the word NEXT just above the lower right button.
• Press the NEXT button once. Now the inlet temp will appear on the screen
Note: the boiler should not be running, so the Outlet & Inlet temp should be the same.
• Press the NEXT button again. Delta T will now appear on the screen
• Press the NEXT button again and DHW will appear on the screen
Page 3