Instruction Manual
Page 2
LAARS Heating Systems
Step 1
Central heating set point
Central heating set point is the desired operating boiler temperature for heating demand.
•While the outlet screen is displayed, press and hold the up arrow for 3-5 seconds
•120 degrees will appear on the screen. This is the default setting from the factory
•Press the up arrow to increase the desired set point
For this example we are using 180 degrees.
•When you reach the desired set point, press the DONE button on the lower left corner of the
display
Note: you must press the DONE button to store the set point. If you forget to press the
DONE button, the control will go back to the default setting of 120 degrees.
•The Central Heat set point is now complete.
Page 2