Instruction Manual
Page 13
Mascot II
Step 4 MASCOT II START UP, CONTINUED
• Turn on the Combustion analyzer and let it purge
• Remove test plug and insert the analyzer in the flue opening provided
• With the boiler powered up, turn on ALL ZONES of heat
• With a call for heat, the system display will go through the firing sequence.
The sequence will read: Check, then Prepurge, then Ignition and Run.
• You will need to adjust the CO
2 percentage on both high and low fire. High fire should be checked first.
This is done by adjusting the firing rate in Diagnostic mode .
DIAGNOSTIC MODE: Is achieved by pressing and holding
the NEXT button for 5 seconds.
NOTE: you must start in the outlet
screen before pressing and holding the next button.
Page 13