Instruction Manual

Page 13
Mascot II
Step 4 MASCOT II START UP, CONTINUED
Turn on the Combustion analyzer and let it purge
Remove test plug and insert the analyzer in the flue opening provided
With the boiler powered up, turn on ALL ZONES of heat
With a call for heat, the system display will go through the firing sequence.
The sequence will read: Check, then Prepurge, then Ignition and Run.
You will need to adjust the CO
2 percentage on both high and low fire. High fire should be checked first.
This is done by adjusting the firing rate in Diagnostic mode .
DIAGNOSTIC MODE: Is achieved by pressing and holding
the NEXT button for 5 seconds.
NOTE: you must start in the outlet
screen before pressing and holding the next button.
Page 13