Manual
Is
There a
Blockage in the
Injector Body or
Venturi Tube?
2211
PPrroobblleemm 11
IInnnneerr
CCoommbbuussttiioonn
CCoonnee WWiillll NNoott
LLiigghhtt
Is
Thermostatic
Head Set to
Maximum?
Is the
Primary Orifice
Plugged on the
Inside or
Outside?
Turn Thermostat
Up to Its
Maximum
Setpoint.
Remove the Primary Burner
Orifice. Clean with a Soft
Brush or Compressed air.
Yes
No
Yes
Yes
Yes
Is the Inner
Combustion Cone
Plugged?
Is There Air or
a Blockage in the
Gas Hose or
Gas Piping?
Remove Blockage with Compressed
Air or Replace the Gas Hose or Pipe
Section. Bleed Off any Air from the
Gas Line.
Clean the Heater.
Clean the Heater.
No
No
No
Is Proper
Gas Pressure
Supplied to the
Zone Panel or
Heater?
Provide 5 PSIG
Gas Pressure.
Yes
No
Are all Fuel
Supply Valves to
Heater Open?
Open All Fuel
Supply Valves.
Yes
No
Defective
Safety Control Valve.
Replace the Safety
Control Valve.
Yes
No