User Manual

D
DEFINING THE TEMPERATURE CURVE
The SmartBox
has the capacity for 10 time and
temperature control periods.
-- An example is the following:
Period DRT Day SmartBox
Set Point
Forced Air Radiant
1 76 F 1 74 F 88 F
2 76 F 7 74 F 85 F
3 76 F 21 74 F 74 F *
4 72 F 35 70 F 60 F
5 70 F
48 68 F 60 F
6 68 F 65 66 F 60 F
7 66 F 70 64 F 60 F
8 64 F 80 62 F 60 F
9 62 F 120 60 F 60 F
10 62 F
180 60 F 60 F
* Typically the radiant heaters will shut off
after 2-3 weeks o
f operation.
Note
:
For each Period, the Days must be equal to or
greater than the previous period.
Example: Period 3 cannot start at Day 6.
SET-UP OF ROOM CONTROL
-- Determine the 10 temperature/day period curve.
-- Enter the temperature curve.(See the previous table
example)
-- Set heat “on” offset to -3F (73F)
-- Set the heat “off” differential to 3F (76F), same as the
DRT
- The SmartBox
will turn heating off before
temperature exceeds DRT or Set-point.
- This allows the SmartBox
to be enabled to
operate in the range of 73F to 76F.
SET-UP OF SYSTEM TEMPERATURE CURVE
Press the up/down keys and the center soft key
simultaneously to enter the set-up mode. The following
screen is displayed.
FIG. 34
Press the right soft key PARAMETERS.
Continue to press the right soft key NEXT to arrive at the
Temperature Curve Input section. See Fig.35.
FIG. 35
To enter the temperature, press the center soft key EDIT.
The following screen is displayed.
FIG. 36
Use the up/down keys to set the Start Temperature for
Zone 1. Press the right soft key NEXT and use the up/down
keys to set Zone 2 Start Temperature.
Press the left soft key DONE.
Press the right soft key NEXT. The following screen is
displayed.
FIG. 37
Press the center soft key EDIT. The following screen is
displayed.
FIG. 38