Owner's manual

Two Times
Flash pattern
begins 12
seconds after
condition
occurs.
(Pattern
indicates
lack of air
proving in fan
section
of unit.)
Are
air-proving switch
contacts stuck open?
(Perform continuity
check.)
Does
fan motor start up
for prepurge
during initial call
for heat?
Is
fan wheel
binding?
Is fan wheel
loose on motor
shaft?
Yes
Yes
Yes
No
Check for binding of
air-proving switch arm
on housing, air-proving
flapper stuck, or out of
adjustment. Repair or
replace as necessary.
Yes
Yes
Check for proper clearance of
fan wheel to motor mount. If
good, replace fan wheel, or
check for housing alignment.
Tighten set screw(s) on fan.
Make sure set screw(s) are
tightened against flat(s) of
motor shaft.
Yes
Clean the fan wheel with
compressed air or soft brush.
Defective motor
or capacitor.
Replace motor.
Yes
Remove obstruction.
Clean as necessary.
No
Is fan wheel
plugged with
dirt?
No
Is there
an obstruction
in blower outlet
preventing air-proving
switch closure?
No
Is
proper voltage
supplied to motor
from ignition
module?
No
If improper voltage is supplied,
contact electrician.
- OR -
If no voltage is supplied to
motor, check wiring, replace
motor relay (if applicable), or
replace ignition control module.
No
Yes
Is
proper
voltage being
sent to air-proving
switch?
Check wiring between
module and component.
Repair or replace as
necessary, or replace
ignition control module.
No
22