Datasheet

For inquires or orders :
Safety Warnings :
Please read the "Safety Warnings" in the instruction manual supplied with the instrument thoroughly and completely
for correct use. Failure to follow the safety rules can cause fire, trouble, electrical shock, etc. Therefore, make sure
to operate the instrument on a correct power supply and voltage rating marked on each instrument.
The contents of this leaflet are subject to change without notice.
In consideration of the environment, soy ink and recycled paper were used in this publication.
KEW 2200-1E Mar. 11 AD
ISO9001:2008
APPROVED BY BUREAU VERITAS Certification
MODEL 8008
Multi-tran
For measurements
up to 3000A AC
Connect the test leads to
the circuit under test.
Press the trigger to open the current sensor
and clamp the one conductor under test.
IncorrectCorrect
●
KEW 2200 Specifications
●
Included Accessories
AC Current Measurement
AC/DC Voltage Measurement
●
Optional Accessories
AC A 40.00/400.0/1000A (Auto-ranging)
±
1.4%rdg
±
6dgt(50/60Hz)
±
1.6%rdg
±
6dgt(45~65Hz)
AC V 4.000/40.00/400.0/600V (Auto-ranging)
±
1.8%rdg
±
7dgt(45~65Hz)
±
2.3%rdg
±
8dgt(65~500Hz)
DC V 400.0mV/4.000/40.00/400.0/600V (Auto-ranging)
±
1.0%rdg
±
3dgt
Ω
400.0
Ω
/4.000/40.00/400.0k
Ω
/4.000/40.00M
Ω
(Auto-ranging)
±
2.0%rdg
±
4dgt(0~400k
Ω
)
±
4.0%rdg
±
4dgt(4M
Ω
)
±
8.0%rdg
±
4dgt(40M
Ω
)
Continuity buzzer buzzer sounds below 50
±
30
Ω
Conductor size
φ
33mm max.
Withstand voltage 5320V AC for 5 seconds(AC A)
3540V AC for 5 seconds(AC/DC V)
Applicable standards IEC 61010-1 CAT.
Ⅲ
600V (AC A),
CAT.
Ⅲ
300V/CAT.
Ⅱ
600V(AC/DC V),
Pollution degree 2
IEC 61010-031, IEC 61010-2-032
IEC 61326(EMC)
Power source R03/LR03(AAA)(1.5V)
×
2
Dimensions 190(L)
×
68(W)
×
20(D)mm
Weight Approx. 120g(including batteries)
Accessories 7107A(Test leads)
、
9160(Carrying case)
、
R03(AAA)
×
2,
Instruction manual
Optional 8008(Multi-tran)
Teardrop shaped jaw for easy use in crowded cable areas
Capable of measuring currents up to 1000A AC
Slim and compact that fits right into your pocket
Standard 4 mm input terminals for ordinary test leads