Spec Sheet
SPECIFICATIONS KPAC2421-2
COOLING CAPACITY
BTU/hr @ 95F at 60% RH 22,900 (2-Ton)
COMPRESSOR DATA
Compressor Type Hermetic Rotary
Operating Temperatures 70-105 F 50%RH
Refrigerant 410A
FAN DATA
Evaporator
Fan Type (Centrifugal) Direct Drive
Air Flow (CFM) 810/1Speed
Supply Air Device 2 - 6" Dia. x 18" Air Chute
Supply Air Duct max. length 25'
Condenser
Fan Type (Centrifugal) Direct Drive
Air Flow (CFM) 1100
Condenser Duct Specs (optional) 1 - 14" Dia. x 8' Length
Condenser Duct Max. Length  25'
ELECTRICAL DATA
Power Supply (Volts)  208/230 Single Phase
Current Consumption (Amps)  10.6/9.6
Power Consumption (kW)  2.0
Maximum Circuit Breaker (Amps)  20
Recommended Breaker Size 20
Minimum Circuit Ampacity (Amps)  14.3
Min./Max. Voltage  195-225/210-250
Power Cord Gauge/Length  12/7'
Plug Configuration  NEMA 6-20
DIMENSIONAL DATA
Width x Depth x Height (Inches)  20.325" x 26" x 44"
Weight (Lbs.)  206
Shipping Weight (Lbs.)  266
Ceiling Kit Weight (Lbs.)  24
Shipping Weight w/ Ceiling Kit  290
SAFETY DEVICE DATA
Compressor Overload  Internal
Fan Motor Overload  Automatic Internal
Evaporator Freeze Protection  Freeze Stat
High Pressure Switch  Manual
Compressor Short Cycle  Yes
Automatic Restart  Yes
Thermostat Type  Microprocessor/Digital
Condensate Pump Overflow  Optional
Condensate Tank Overflow  Yes
1-800-KWIKOOL
www.kwikool.com


