Instructions

System with online functionality
© KUNBUS 65
Figure 59: Screen Test with PLC
In the following the online functions Tests with PLC are listed:
Baud rate detection (chapter 8.1)
Generate livelist (chapter 8.2)
Rotation time (chapter 8.3)
Signal level measurement (chapter 8.4)
Signal level summary list (chapter 8.5)
Event log (chapter 8.6)
Event count (chapter 8.7)
Diagnostic event (chapter 8.8)
The DP Slave oriented signal level measurement can be
very time-consuming in connection with low baud rates or
low data traffic.
The NetTEST II can be connected directly to a free
PROFIBUS plug in the network. Also, connection between a
PROFIBUS plug and the respective DP Slave via an adapter
cable (PROFIBUS Y-cable, see accessories) is possible. In
general, you should exercise care in connecting the
NetTEST II to running bus systems. At higher baud rates
( 1.5 Mbit) spur lines are strictly forbidden, because the data
traffic may be significantly disrupted.