Instructions

Systems with PROFIBUS Master Option
© KUNBUS 57
The Slave communication state is shown on the last display
line. Thus, the user can check every time whether the
communication with the Slave functions or whether a
parameter / configuration problem persists.
Possible messages on this line could be:
"No Answer"
No communication with the Slave can be established
(e.g. wrong address).
"Param_Fault !"
Parameterization of the Slave is incorrect.
"Cfg_Fault !"
Configuration data of the Slave are incorrect.
"Not_Ready"
The Slave is not (yet) ready for data exchange.
"Param_Req !"
The Slave expects parameterization by the Master.
"DATA_EXCHANGE"
The Slave was properly parameterized and configured.
Data exchange is taking place
"DATA_EXCHANGE !"
The diagnostic data at the Slave has changed. By
selecting the menu 7.3.2.10 Show Slave diagnostic the
diagnostic data can be displayed and the '!' in the
display will be acknowledged.
There is an additional submenu for changing the configuration
data or the output data or displaying the input data of the Slave.