Instructions

NetTEST II Menu Guide
© KUNBUS 11
The PROFIBUS baud rate, address and slot time are necessary
for the parameterization of the installed PROFIBUS Master.
With these settings, the tests Generate livelist, Slave ident
number, as well as Slave signal quality are executed.
Moreover, indications regarding number of:
Connectors (only number of 12 Mbit/s plugs!)
Devices (all devices with PROFIBUS plug, or connected
cable)
Connected devices and 12 Mbit/s PROFIBUS plugs
considerable change by their inductivity resp. capacity the
measuring abilities and characteristics for the NetTEST II. In
order to keep these measuring insecurities in a tolerable scale,
please indicate before each measurement the number of
installed 12 Mbit/s plugs as well as the number of the devices
connected to the bus. Please only indicate the plugs which
dispose of incorporated direct-axis inductances. Devices stand
for all units connected to a bus segment. This applies to Master
and Slaves as well as to net components like segment couplers,
repeaters, optical couplers etc.
Once the data are stored in the data base, they can always be
used for new tests. The data in this data base cannot be deleted,
only changed by overwriting. In order to have enough spare
capacity for this function, 20 memory locations are available.
The respective memory locations can be reached by actuating
the or the key.