Instructions

NetTEST II Menu Guide
© KUNBUS 9
5.2.1 Test without PLC
The menu Test without PLC serves for stepwise physical
analysis of lines. This means that the test can be executed as
often as desired. Some tests are based on the reference data of
the preceding test, so that this one must be run beforehand. The
individual items are interlocked, so that wrong operation is
impossible. For test runs under this menu, no protocol is made
out.
Figure 4: Screen ‘Test without PLC’
For a line test, at first the design parameters for the PROFIBUS
segment that has to be checked must be indicated. These
indications are necessary, so that, e.g. the PROFIBUS DP
specific measurements at the line segment may be executed
with the real bus settings used in your plant. The settings are
made in the submenu Segment list.
As soon as an option is activated (DP Master or Online
Function), the Line test menu appears under Test
without PLC.