5 Configuration
5.1 Supported Size of the Process Data
The gateway component for DeviceNet supports process data of a
length up to 64 bytes.
An additional 448 bytes are available for the asynchronous data
traffic.
NOTICE
Bear in mind that the maximum length of the process data is always
determined by the fieldbus with the shorter data length.
5.2 Setting MAC-ID and bitrate
The MAC-ID and bitrate are assigned in binary format.
You can set the MAC ID via the DIP switches 1-32, and via switches
S1 and S2 you can set the bitrate.
Set an address switch to "OFF" to switch bit value 0 or to "ON" to
switch bit value 1.
Valid value range for the bitrate:
Valid value range for the MAC-ID: 0-63
Example: Here, you can see the switch setting for the MAC address
42 and the bitrate 500 kBit/s.
Designation S2 S1 32 16 8 4 2 1
Switch setting on off on off on off on off
Configuration