Data Sheet

130130
91
4,25
max. 10,5
7
45
48
48
15,5
91 [3.583]
4,25 [0.167]
max. 10,5 [0.413]
7 [0.276]
45 [1.77]
48 [1.89]
48 [1.89]
15,5 [0.61]
91 [3.583]
4,25 [0.167]
max. 10,5 [0.413]
7 [0.276]
45 [1.77]
48 [1.89]
48 [1.89]
15,5 [0.61]
45
+0,6
[1.772
+0.024
]
45
+0,6
[1.772
+0.024
]
www.kuebler.com © Fritz Kübler GmbH, subject to errors and changes. 10/2016
Terminal assignment
Output 1
Output 2
Power
supply
Pin Signal and control inputs
1 Sensor power supply
AC: 24 V DC / 80 mA
DC: U
B
interconnected
2 GND (0 V DC)
3 INP A (Signal input A)
4 INP B (Signal input B)
5 RESET (Reset input)
6 LOCK (Key locking input)
7 GATE (Gate input)
8 MPI (User input)
Pin Additional connections
924-4
16 Relay contact N.C.4 output 4
17 Relay contact C.4 output 4
18 Relay contact N.O.4 output 4
19 Relay contact N.O.3 output 3
20 Relay contact C.3 output 3
Pin Version with relays/optocouplers
9 Relay contact C. / Kollektor
10 Relay contact N.O. / Emitter
11 Relay contact C. / Emitter
12 Relay contact N.O. / not assigned
13 Relay contact N.C. / Collector
14 AC: 24 V AC,
100 ... 240 V AC, ±10 % N~
DC: 10 ... 30 V DC
15 AC: 24 V AC,
100 ... 240 V AC, ±10 %
L~
DC: GND (0 VDC)
Pin Additional connections
924-6
16 Common-Emitter output 3 to 6
17 Collector 6 output 6
18 Collector 5 output 5
19 Collector 4 output 4
20 Collector 3 output 3
Panel
cut-out
Preset counters, electronic
Dimensions
Dimensions in mm [inch]
LCD preset counters Codix 923 / 924Multifunctional – pulse, frequency, time – 1...6 presets (AC+DC)