Response time of the outputs:
1-channel operation < 100 ms @ 40 kHz
< 350 ms @ 65 kHz
2-channel operation < 150 ms @ 40 kHz
< 600 ms @ 65 kHz
10.4 Timer
Seconds 0.001 s ... 999 999 s
Minutes 0.001 min ... 999 999 min
Hours 0.001 h .. 999 999 h
h.min.s 00h.00min.01s ...
99h.59min.59s
Min. time measurable 500µs
Measuring error < 50 ppm
Response time of the outputs:
Relays < 13 ms
Optocoupler < 1 ms
10.5 Signal and Control inputs
SELV circuits, reinforced / double insulation
Polarity: programmable NPN/PNP
for all inputs in common
Input resistance 5 kΩ
Pulse shape any
Switching level with AC supply:
HTL level Low: 0 ... 4 VDC
High: 12 ... 30 VDC
4-30 V level Low: 0 ... 2VDC
High: 3,5 … 30 VDC
Switching level with DC supply:
HTL level Low: 0 ... 0,2 x UB
High: 0,6 x UB ... 30 VDC
4-30 V level Low: 0 ... 2 VDC
High: 3,5 ... 30 VDC
Minimum pulse length of the Reset input: 1 ms
Minimum pulse length of the Control inputs:10 ms
10.6 Outputs
Output 1
Relay with make contact
Prescribed fuse: 3A
programmable as NC or NO
Switching voltage max. 250 VAC/ 110 VDC
Switching current max. 3 A AC/ V DC
min. 30 mA DC
Switching capacity max. 750 VA / 90 W
The maximum values shall in no case be
exceeded!
Mechanical service life (switching cycles) 2x10
7
N° of switching cycles at 3 A/ 250 V AC 1x10
5
N° of switching cycles at 3 A/ 30 V DC 1x10
5
or NPN optocoupler
Switching capacity 30 VDC/10 mA
U
CESAT
for IC = 10 mA: max. 2.0 V
U
CESAT
for IC = 5 mA: max. 0.4 V
Output 2
Relay with changeover contact
Prescribed fuse: 3A
Switching voltage max. 250 VAC/ 150 VDC
Switching current max. 3 A AC/ A DC
min. 30 mA DC
Switching capacity max. 750 VA/ 90 W
The maximum values shall in no case be
exceeded!
Mechanical service life (switching cycles) 20x10
6
N° of switching cycles at 3 A/ 250 V AC 5x10
4
N° of switching cycles at 3 A/ 30 V DC 5x10
4
or NPN optocoupler
Switching capacity 30 V DC/10 mA
U
CESAT
for IC = 10 mA: max. 2.0 V
U
CESAT
for IC = 5 mA: max. 0.4 V
10.7 Supply voltage
AC supply: 100 ... 240 V AC / max. 9.5 VA
50/ 60 Hz, Tolerance ± 10%
ext. fuse protection: T 0.1 A
24 VAC +/- 10% / max. 6 VA
50 / 60 Hz
ext. fuse protection: T 0,315 A
DC supply: 10 ... 30 V DC/ max. 5 W
reverse polarity protection
SELV, CLASS II (Limited
Power Source)
ext. fuse protection T 0.2 A
10.8 Sensor supply voltage
(Voltage output for external sensors)
SELV circuits, reinforced / double insulation
for AC supply: 24 V DC ±15%, 80 mA
for DC supply: max. 80 mA, external voltage
supply is connected through
10.9 Climatic Conditions
Operating temperature: -20°C .. +65°C
Storage temperature: -25°C .. +75°C
Relative humidity: RH. 93% at +40°C,
non-condensing
Altitude: to 2000 m
10.10 EMC
Noise immunity: EN 61000-6-2
with shielded signal and
control cables
Noise emission: EN 55011 Class B