Datasheet
135135
Z1500
6.560.010.XXX
www.kuebler.com© Fritz Kübler GmbH, subject to errors and changes. 10/2016
Preset
counters
Display 6-digit red 14 segment LED display,
14 mm [0.55] high
Operating temperature -20°C ... +65°C [-4°F ... +149°F]
(non-condensing)
Storage temperature -25°C ... +75°C [-13°F ... +167°F]
Relative humidity at +40°C [+104°F] RH 93 % (non-condensing)
Altitude up to 2000 m [6562‘]
Count inputs A and B
Polarity of the inputs programmable for all inputs
in common, NPN/PNP
Input resistance 5 kΩ
Count frequency pulse counters max. 55 kHz
tachometers max. 65 kHz
can be damped to 30 Hz
(mechanical contacts)
(
details s. instruction manual)
Control / Reset input
MPI 1 and MPI 2,
Lock, Gate, Reset
Min pulse duration of the inputs
10 ms /1 ms
Switching levels HTL-level: LOW: 0 ... 4 V DC
with AC supply HIGH: 12 ... 30 V DC
4 ... 30 V DC: LOW: 0 ... 2 V DC
HIGH: 3.5 ... 30 V DC
Switching levels HTL-level: LOW: 0 ... 0.2 x U
B
with DC supply HIGH: 0.6 x U
B
... 30 V DC
4 ... 30 V DC: LOW: 0 ... 2 V DC
HIGH: 3.5 ... 30 V DC
Pulse shape variable, Schmitt-Trigger
characteristics
Switching voltage max. 250 V AC / 150 V DC
Switching current max. 3 A AC / DC
min. 30 mA DC
Switching capacity max. 750 VA / 90 W
Output 1 + 2
mech. service life (switching cycles) 2 x 10
7
N° of switching cycles at 3 A / 250 V AC 5 x 10
4
N° of switching cycles at 3 A / 30 V DC 5 x 10
4
relay with changeover contact
Reaction time of the outputs
13 ms
(pulse / time) (
details s. instruction manual)
General technical data Inputs
Outputs
Protection IP65 (from the front)
Weight approx. 180 g [6.35 oz]
Power supply AC 100 ... 240 V AC, ±10 %
max. 11 VA, 50/60 Hz
DC 10 ... 30 V, max. 5.5 W
External fuse protection 230 V AC T 0.1 A
10 ... 30 V DC T 0.25 A
Data retention > 10 years, EEPROM
Response time of the frequency meter 100 / 600 ms
(details s. instruction manual)
Input modes pulse counters count direction (cnt.dir),
difference (up.dn),
addition A+B (up.up),
phase discriminator x1, x2, x4
(quad, quad x2, quad x4),
ratio (A/B),
ratio in % ((A-B)/A x100 %)
frequency meter A, A-B, A+B quad,
A/B, (A-B)/A x 100 %
timer 4 start modes: FrErun,
Auto, InpA.InpB., InpB.InpB.
Sensor power supply AC supply 24 V DC ±15 %, 80 mA
DC supply max. 80 mA, external power
supply is connected through
EMC standards EN 55011 class B,
EN 61000-6-2, EN 61000-6-3
Device safety designed to EN 61010 part 1
protection class 2
application area pollution level 2
UL approval file E128604
Mechanical characteristics
Electrical characteristics
Count frequency max. 45 kHz
(
details s. instruction manual)
Interface RS232, RS485
Baud rate 9600
Device address 1 ... 99, programmable
Optional interface MODBUS and CR/LF
Terminal assignment
Output 2
Output 1
Power
supply
Pin Signal and control inputs
1 INP A (Signal input A)
2 INP B (Signal input B)
3 RESET (Reset input)
4 LOCK (Keypad lock)
5 GATE (Gate input)
6 MPI 1 (User input 1)
7 MPI 2 (User input 2)
8 Sensor power supply
AC: 24 V DC/80 mA
DC: U
B
connected through
9 Shared connection for signal
and control inputs GND (0 VDC)
Pin RS232
(optional)
22 GND
23 RXD
24 TXD
25 –
26 –
Pin RS485
(optional)
22 –
23 DO
24 DI
25 –
26 –
Pin Version with relay/optocoupler
10 Relay contact C.2
11 Relay contact N.O.2
12 Relay contact N.C.2
13 Relay contact C.1
14 Relay contact N.O.1
15 Relay contact N.C.1
16 AC: 100 ... 240 V AC, ±10 %, N~
DC: 10 ... 30 V DC
17 AC: 100 ... 240 V AC, ±10 %, L~
DC: GND (0 V DC)
Preset counters, electronic
LED preset counters Codix 560
Multifunctional – pulse, frequency, time –
65
kHz, 2 presets (AC+DC)
Technical data