Manual
Page 6 | ENG 
Screw terminals 1 and 3: 
Counting input and reset input
Optocoupler input 10…260 V AC/V DC
galvanic isolation, active for High signal
Min. pulse duration:  16 ms
Max frequency:  approximately 30 Hz
Low level:    0…2 V AC/V DC
High level:    10…260 V AC/V DC
Input resistance:  approximately 160 kOhm
AC mains frequency:  50/60Hz
Screw terminal 2: 
Common AC/DC, common connection for the optocoup-
ler inputs (screw terminals 1 and 3).
Screw terminal 4:
Electrical locking of the reset key
Contact input / Open Collector NPN 
(switching at 0 V DC)
Low level:  0…0.7 V DC
High level:  3…5 V DC
Input resistance: 
    approximately 2.2 MOhm
Input not active: 
    Reset key locked
Input in contact with GND:
    Reset key unlocked
Screw terminal 5:
Function: see table 3, active for negative edge
Contact input/Open Collector NPN
(switching at 0 V DC)
Low level:    0…0.7 V DC
High level:    3…5 V DC
Min. pulse duration:  50 ms
Input resistance:  ca. 2.2 MOhm
Input High:    - - -
Input Low:    Reset of the counter
      Dynamic resetting behaviour
Screw terminal 6:
Common GND connection for screw terminal 4 (reset 
key locking input) and screw terminal 5 (reset input).
Screw terminal 7: 
(–) external power supply for the backlight option
Screw terminal 8:
(+) external power supply for the backlight option
(24 V ±20%, 50 mA), Fuse T0.08 A, delayed action
All low voltages, SELV, reinforced/double 
insulation.
 Signal inputs must be protected with an exter-
nal delayed T0.01 A fuse when the source 
does not provide protective impedance (fuse/
current limitation).
Scope of delivery: 
Digital dispay 
Clamp 
Front frame for screw mounting,     
Panel cut-out 50 x 25 mm
Front frame for clamp mounting,     
Panel cut-out 50 x 25 mm
Seal
Operating instructions 
Note:
This product includes a lithium battery. Do 
not open it by force, do not throw it in the 
fire. Avoid temperatures below –20 °C and 
above +70 °C!
t
!
DANGER