Datasheet

4
48 [1.89]
48 [1.89]
45 [1.772]
16
[0.63]
63.2 [2.489]
3 [0.118]
max. 10.5 [0.413]
55 [2.166]
55 [2.166]
45 [1.772]
62.2 [2.449]
16
[0.63]
4 [0.158]
max. 9.5 [0.374]
50 [1.969]
75 [2.953]
63 [2.481]
45 [1.772]
16
[0.63]
62,2 [2.449]
4 [0.158]
max. 9.5 [0.374]
50 [1.969]
60 [2.363]
48 [1.89]
48 [1.89]
45 [1.772]
16
[0.63]
63.2 [2.489]
3 [0.118]
max. 10.5 [0.413]
55 [2.166]
55 [2.166]
45 [1.772]
62.2 [2.449]
16
[0.63]
4 [0.158]
max. 9.5 [0.374]
50 [1.969]
75 [2.953]
63 [2.481]
45 [1.772]
16
[0.63]
62,2 [2.449]
4 [0.158]
max. 9.5 [0.374]
50 [1.969]
60 [2.363]
1
2
3
4
5
6
7
1
2
3
4
5
6
7
www.kuebler.com © Fritz Kübler GmbH, subject to errors and changes. 03/2023www.kuebler.com
Preset counters, electronic
LCD preset counters 9011 preset – pulse, time (battery)
Terminal assignment 12 ... 250 V AC/DC
Terminal assignment NPN
Example of connection 12 ... 250 V AC/DC
Example of connection NPN
Reset
Reset
Count /
Start
Count /
Start
Key
locking
Key
locking
12 ... 250
V AC / V DC
Pin Inputs / outputs
1 +3 V DC for terminal 2
2 Keyboard lock-input
3 Relay contact
4 Relay contact
5 AC/DC optocoupler count input
6 AC/DC optocoupler reset input
7 Common AC/DC input for terminal
6 and 5
Pin Inputs / outputs
1 +3 V DC for terminal 2
2 Keyboard lock-input
3 Relay contact
4 Relay contact
5 NPN count/start input
6 NPN reset input
7 Common AC/DC input for terminal
6 and 5
Programming
The counter is programmed using the keys on the front. The user is guided by
plain text on the display.
The following modes are programmable:
1. Function: pulse preset counter or preset timer
2. Count mode (adding or subtracting)
3. Output: permanent signal or timed signal in case of automatic repetition
(loop)
4. Output (normally open or normally closed)
5. Timed signal duration (Delay) in case of automatic repetition
0.1 … 99.9 seconds
6. Decimal point up to max. 5 decimal places (pulse counter)
or up to max. 2 decimal places (preset timer)
7. Time range for the preset timer: seconds minutes, hours
Function of the output
Adding:
Relay is active , when actual value preset
Subtracting:
Relay is active , when actual value 0
In case of automatic repetition, the output signal is a timed signal programmable
in 100 ms steps from 0.1 to 99.9 seconds.
A colon is displayed on the lower display line when the relay is activated.
An indicator flashes at one-second intervals when timing is active.
Operating the counter
Setting or resetting:
Press the red SET button or apply a pulse to the reset input to set the counter
to zero in the adding mode or to the preset in the subtracting mode.
Presetting:
The preset value is indicated on the lower row of digits. To set it, use the 6
presetting buttons assigned to each decade. The set value will be accepted
with the next set or reset operation.
Overflow and underflow:
In the adding mode the overflow is 999 999 to 0; in the subtracting mode it
is 0 to 999 999. The output signal remains unaffected.
Lo-bat-indicator:
When the battery charge is too low, Lo-bat appears in the lower display.
This flashes on a two second cycle. When lo-bat is indicated, the battery
should be changed as soon as possible. If the charge goes on decreasing,
the device switches to (noFunc) “no function” mode and must be
reprogrammed.
Changing the battery:
The unit retains the programmed values if the batteries are replaced within
2 minutes. Otherwise, the device must be re-parameterized.
Counting:
By means of positive pulses (12 … 250 VAC) or by a NPN input pulse.
Time counting remains active as long as the counter input is active
(preset timer).