Manual

Installation and operating instructions 38 BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
1 = counter
operates
Bit 1: Counter reset
0 = no function
1 = reset the
counter
3091H 05H 0
Controlling batching
process
without byte 0 3 w - d
Bit 0: 1 = Start filling through bus,
only at batching process = CAN
Bus (0 = without function)
Bit 1: 1 = Stop filling through bus,
independent from other inputs (0 =
without function)
3091H 06H 0 Learning function - byte 0 3 r/w - d Self learning function
Bit 1-0: Activation of function
0 = function off
1 = not allowed
2 = function on,
no other action
3 = function on
and the next
filling starts the
self learning cycle
3091H 07H 0
Function select for ‘switch
off calculation’
- byte 0 1 r/w - d
Programm select for switch off
calculation
0 = switch off point depends from
the last 1 to 5 tail volumes
1 = switch off point depends from
the actual flow and the last 1 to 5
tail volumes
3091H 08H 0 Function data 1 - byte 0 5 r/w - d
First data for the function ‘switch off
calculation’
Fct = 0: number of tail volumes for
switch off calculation (1 to 5)
Fct = 1: number of tail volumes for
switch off calculation (1 to 5)
3091H 09H 0 Function data 2 - byte 0 255 r/w - d
Second data for the function ‘switch
off calculation’
(for future use)
3091H 0AH 0,001
Volume flow value for
switch off
l/s float 0 15,1 r/w - d
If the volume flow is lower then this
value, the filling will stop after
number of measurements
3091H 0BH 10 Number of measurements byte 1 100 r/w - d Parameter for the function 3091.10
3091H 0CH 0 Definition for shut-down without byte 0 63 r/w - d
Bit 0: 1 = output 1 switch off if
3091_05 Bit 1 = 1 , 0 = no
influencing of the output
Bit 1: 1 = output 2 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output
Bit 2: 1 = output 3 switch off if
3091_05 Bit 1 = 1 , 0 = no
influencing of the output
Bit 3: 1 = output 4 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output
Bit 4: 1 = output 5 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output
Bit 5: 1 = output 6 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output
3091H 0DH 100 Fixed tail volume 1 ml byte 0 255 r/w - d
this tail volume is used for the next
filling (if the bit 4 is set in RPDO1)
and after power on
3091H 0EH 100 Fixed tail volume 2 ml byte 0 255 r/w - d
this tail volume is used for the next
filling (if the bit 5 is set in RPDO1)
3091H 0FH 10
Percentage of target
volume
% byte 0 50 r/w - d
this tail volume is used for the next
filling (if the bit 6 is set in RPDO1)
3092H Status values and PDO definition
3092H 00H 2 Number of entries without byte - - r - d
3092H 01H 0 Actual status of batching without byte 0 5 r 91H -
Bit 0-3: actual status of batching
0 = stop