Manual
Installation and operating instructions
BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
1000 = switch off
by analogue
voltage
1001 = switch off
by batch program
1010 = switch off
by error detected
1011 = switch off
by customer
program
30y4H 06H
0,001
s
Off value
l or s or l/s
or V or °C
float
0s
0l
0l/s
0V
-20°C
100s
100l
15l/s
11V
120°C
r/w - d
According to selected function: off
time or volume or volume flow or
temperature or voltage
30y4H 07H 0 Input channel for off signal without byte 0 21 r/w - d
Bit 0-3: input channel for output off
function
0000 = function 1
0001 = function 2
0010 = function 3
0011 = function 4
0100 = function 5
0101 = function 6
Bit 4: Calculation function
0 = input >
parameter
1 = input <
parameter
30y4H 08H 0 Status of output without byte 0 7 r/w y4H - Bit 0: actual status of output
0 = output is off
1 = output is on
Bit 2-1: error status of output
00 = no error
01 = short circuit
(only detected if
output is on)
10 = interruption
(only detected if
output is on)
11 = chip
temperature to
high
30y4H 09H 4
Sending function for Index
08H
without byte 0 4 r/w - d
Bit 3-0: Sending function change of
status
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
309xH Batching
3091H Filling parameter
3091H 00H 15 Number of entries without byte - - r - d
3091H 01H 0,5 Target volume l float 0,0001 200 r/w - d
Automatic output controls on this
parameter
3091H 02H 0,02 Forward run time s float 0.01 10 r/w - d
Time after starting, before opening
of valve
3091H 03H 0,5 Time out s float 0.01 10 r/w - d
Time after filling, before a new run
instruction is accepted
3091H 04H 1 Counter control without byte 0 3 w - d
Counter control (only active on
manual control output))
Bit 0: Start/Stop Counter
0 = stop counter