Manual

Installation and operating instructions 36 BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
ground
1 = output
switching to +24V
Bit1: output polarity
0 = high active
1 = low active
30y4H 02H 0
Output on function
definition
without byte 0 11 r/w - d
Bit 0-3: definition for switching the
output on
0000 = without
function (off)
0001 = switch on
by input
0010 = switch on
by bus
0011 = switch on
by time
0100 = switch on
by volume
0101 = switch on
by volume flow
0110 = switch on
by fluid
temperature
0111 = switch on
by electronic
temperature
1000 = switch on
by analogue
voltage
1001 = switch on
by batch program
1010 = switch on
by error detected
1011 = switch on
by customer
program
30y4H 03H
0,001
s
On value
l or s or V or
°C
float
0s
0l
0l/s
0V
-20°C
100s
100l
15l/s
11V
120°C
r/w - d
According to selected function: on
time or volume or volume flow or
temperature or voltage
30y4H 04H 0 Input channel for on signal without byte 0 31 r/w - d
Bit 0-3: input channel for output on
function
0000 = function 1
0001 = function 2
0010 = function 3
0011 = function 4
0100 = function 5
0101 = function 6
Bit 4: Calculation function
0 = input >
parameter
1 = input <
parameter
30y4H 05H 0
Output off function
definition
without byte 0 11 r/w - d
Bit 0-3: definition for switching the
output off
0000 = without
function (off)
0001 = switch off
by input
0010 = switch off
by bus
0011 = switch off
by time
0100 = switch off
by volume
0101 = switch off
by volume flow
0110 = switch off
by fluid
temperature
0111 = switch off
by electronic
temperature