Manual

Installation and operating instructions
BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
0010 = start of
batching
0011 = stop of
batching
(emergency shut-
down)
0100 = customer
program
Bit 4: Calculation function
0 = input >
parameter
1 = input <
parameter
30y3H 02H 1,0
Scaling factor for analogue
input
without float 0,0001 1000 r/w - as
The measured analogue voltage [V]
is multiplied with this factor
30y3H 03H 0,0
Scaling offset for analogue
input
V float -1000 1000 r/w - as
The offset is added to the
measured analogue voltage [V]
(voltage = offset + factor*real
voltage)
30y3H 04H 0,0
Measured voltage (with
scaling)
V float 0,0 1000 r y2H - actual measured voltage
30y3H 05H 4
Sending function for Index
04H
without byte 0 4 r/w - d
Sending function of analogue value
(repeat time depends on index 6)
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
30y3H 06H 250 Repeat time ms word 50 5000 r/w - d Repeat time for the value
30y3H 07H 10 Maximum voltage V float 0,0001 12,0 r/w - d
Limit value for voltage with
emergency shut-down
30y3H 08H 0 Definition for shut-down without byte 0 63 r/w - d
Bit 0: 1 = output 1 switch off if
voltage is to high, 0 = no
influencing of the output
Bit 1: 1 = output 2 switch off if
voltage is to high, 0 = no
influencing of the output
Bit 2: 1 = output 3 switch off if
voltage is to high, 0 = no
influencing of the output
Bit 3: 1 = output 4 switch off if
voltage is to high, 0 = no
influencing of the output
Bit 4: 1 = output 5 switch off if
voltage is to high, 0 = no
influencing of the output
Bit 5: 1 = output 6 switch off if
voltage is to high, 0 = no
influencing of the output
30y3H 09H 0 Actual status without byte 0 1 r y3H -
Bit 0: 1 = Limit value exceeded, 0 =
okay
30y3H 0AH 4
Sending function for Index
09H
without byte 0 4 r/w - d Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
30y4H Binary output parameter and PDO definition (only valid if 30y1.1 = 03H)
30y4H 00H 9 Number of entries without byte - - r - -
30y4H 01H 0 Output hardware function without byte 0 3 r/w - d
Bit 0: definition for high or low side
driver
0 = output